Industrial Registers Models ER-10, ER-10/R & ER-10H Digital Resettable Totalizer and Rate of Flow Indicator ER-10 ER-10H For Portable Large Meter Tester Only This product contains Lithium batteries. Read this manual before attempting any installation, wiring or operation.
Model ER-10, ER-10/R & ER-10H Industrial Register Page ii March 2014
User Manual CONTENTS About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation . . . . . . . . .
Model ER-10, ER-10/R & ER-10H Industrial Register Page iv March 2014
User Manual ABOUT THIS MANUAL This manual contains information concerning the installation, operation and maintenance of the Badger Meter® ER-10, ER-10/R (Remote) and ER-10H electronic registers. Installing, wiring and programming these units is fairly simple and straightforward. This manual provides you with a step-bystep guide for this purpose. Examples are provided only to illustrate the programming function.
Model ER-10, ER-10/R & ER-10H Industrial Register INSTALLATION Panel Installation Slide the included gasket over the rear of the unit. Place the unit in the panel through a 33 mm x 68 mm cutout. Use the provided panel mount screws to tighten the mounting clips until there is a secure seal against the gasket. Do not over tighten. Slide the mounting clips into the grooves in the side of the ER-10. Gasket installed 2.677" (68 mm) Recommended Panel Cutout 1.
User Manual WIRING INSTRUCTIONS Wiring Terminals Rear View RST 4 Reset IN B 2 Count Input GND 1 Ground 7 +10-30VDC 6 DC Common Program enable 5 Enable/R 5 Enable/R Figure 3: Wiring terminals Terminal 1 2 3 4 5 6 7 Function Ground Input B Count input — Reset Program enable Backlight common Backlight power Operation — Count input Contact closure of NPN 100 Hz max Not used Connect to ground to reset totalizer. This is a maintained or level-sensitive reset. Connect to ground to enter program mode.
Model ER-10, ER-10/R & ER-10H Industrial Register OPERATION Display Types 34675890 Figure 4: Total display R 2345 Figure 5: Rate display Total Display Total Display indicates the present count value, which is equal to the number of pulses received (since the last reset) multiplied by the Totalizer Scaler Value in Program Mode 1. Rate Display Rate Display indicates the rate value, which is equal to the input frequency multiplied by the Rate Prescale Value in Program Mode 3.
User Manual PROGRAMMING IIMPORTAN You must connect terminals 1 and 5 together to enable the programming mode. After all programming is complete, remove the connection between terminals 1 and 5 to prevent the unit from being reprogrammed by mistake. To access the programming screens, press and hold the key while repeatedly pressing the key until the Program Mode (1 through 6) you want displays on the screen. 1 01.
Model ER-10, ER-10/R & ER-10H Industrial Register PROGRAMMING CALCULATIONS Totalizer Programming Totalizer values can be expressed in any engineering unit of measure such as gallons, quarts, or liters. For each unit, a unique scale factor must be programmed.
User Manual Pulse Output Programming The Pulse Output can be programmed for any engineering unit of measure. A Pulse Output Scale Factor must be calculated and programmed (Program Mode 6) using the same formula and procedure as described under the Totalizer Scale Factor (Program Mode 1).
Model ER-10, ER-10/R & ER-10H Industrial Register TROUBLESHOOTING Problem Possible Causes Remedies Screen is blank Battery is dead. Replace battery. Will not count in totalizer mode 1. 2. 3. 4. Improperly programmed. Broken or defective wiring. Improperly connected. Transmitter defective. Will not indicate rate of flow 1. Improperly programmed. 2. Improperly connected. 3. Transmitter defective. 1. 2. 3. 4. Check programming. Check wiring. Check connections.
User Manual FIELD CALIBRATION Field calibration consists of determining the exact transmitter pulse output per unit of measure for your particular meter/ transmitter combination and then using this value as the transmitter pulse output value when calculating the counter and time base values. The procedure is as follows: 1. Set the Totalizer Scale Factor (Program Mode 1) to 01.0000. 2. Set the Totalizer Decimal Point (Program Mode 2) to 000000. 3. Reset the counter to 0. 4.
Model ER-10, ER-10/R & ER-10H Industrial Register Replacing the Meter's Sensor Pickup Oscillating Piston Industrial Turbo Disc Figure 6: Meter mount components To replace the sensor pickup on your meter, follow these steps: Industrial turbo meter 1. 2. 3. 4. Remove the front cover from the ER-10 unit and disconnect all wiring. Remove meter head bolts and the lift the meter head assembly from the housing. Remove the retaining ring that holds the accessory unit to the head.
User Manual SPECIFICATIONS Power Rate Indicator Internal battery 3V, Lithium Digits 4/5, (4 calculated, 5 displayed with fixed zero in LSD) Battery life 5 years expectancy Scaler range 0.
Control. Manage. Optimize. Recordall is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. © 2014 Badger Meter, Inc. All rights reserved. www.badgermeter.