Specifications

Installation Data
The holes are 0.19 inches in diameter. This allows a variety of other mounting hardware to be used.
Alternative Bracket
The ORION remote endpoint can also be mounted to an alternative bracket (not supplied).
At least two mounting holes must be used to secure the endpoint to the bracket.
After the ORION remote endpoint is mounted, connect the wire to the gas meter terminals or to the gas RT wires.
WIRING CONNECTION INSTRUCTIONS
There are three types of wiring connections:
1. to a volume corrector
2. to a gas RT with gel caps
3. to an alternative electric or mechanical switch closure
Regardless of the mounting method, the remote endpoint should be mounted so the wire exits the module bottom.
The wire should be secured to the pipeline or other stationary object using cable ties (not supplied) or other means.
The remote ORION remote endpoint is supplied with a six (6) foot long cord, 3-conductor cable.
The wires can be extended to up to 75 feet.
Cable
Strain Relief
Cable to
Pulse Source
Screw Holes
and Screws
(4-11)
Page 13