User guide
Compact Digital Flow Monitor, Model B3000
Page 44 March 2014
A
B
C
D
E
F
G
H
THIS DRAWING IS PROPRIETARY TO BADGER METER INC. RECEIPT OR POSSESSION CONFERS NO RIGHT TO USE
THE SUBJECT MATTER OF THIS DRAWING OR TECHNICAL INFORMATION SHOWN; NOR THE RIGHT TO REPRODUCE THIS
DRAWING OR ANY PART EXCEPT FOR THOSE SUPPLIERS OF BADGER METER INC. WHO RECEIVE A WRITTEN
REQUEST FOR MANUFACTURE OR SIMILAR USE.
NOTES: UNLESS OTHERWISE SPECIFIED
3. RADII TO BE .005/.010
2. FINISH TO BE 63
1. REMOVE ALL BURRS AND BREAK SHARP EDGES .005/.010
2 1345610 9 8 712 11
REVISIONS
F
G
H
ZONE REV DESCRIPTION E.C.N. DAT E APPROVAL
H10 A
1.) WAS Voc=2.5V
- 3/19/12
H10
2.) WAS Isc=1.8mA
B
A
C
D
E
PART NUMBER:
TEL: 262-639-6770 FAX: 262-639-9857
RACINE, WISCONSIN U.S.A.
B300020
B300020
1 OF 1
12
11
10 9 8
7
6
5
4 3
2
1
WILL BE IGNORED UNLESS AUTHORIZED.
SCALE: SHEET:CURRENT REV:NONE A
D
59380
THIS DRAWING WAS DONE ON AUTOCAD AND
CAN ONLY BE REVISED ON AUTOCAD SYSTEM.
ANY MANUAL CHANGES DONE TO THIS DRAWING
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOLERANCE ON DECIMALS
SUPERSEDES:
DATE:
CHECKED BY:
DRAWN BY:
ENGINEER:
MATERIAL:
CODE I.D. NO.SIZE: PART NUMBER:
.00 ±.010, .000 ±.005
ANGLES ±1/2°
REVISED BY:
NAME:
BADGER METER
T. PAUL
12/2/09
T. PAUL 3/19/12
INSTALLATION DRAWING FOR
B3000 MONITOR
NOTES ON CABLE ENTRY
NOTES ON CONTROL EQUIPMENT
WITH RESPECT TO EARTH.
1. CONTROL EQUIPMENT MUST NOT USE OR GENERATE MORE THAN 250 V,
Li + Lc
Ci + Cc
Imax
Vmax
IS EQUIPMENT
PART 1, SEC. 18 AND APPENDIX F, ARTICLE 500 OF THE NEC, OR
MANUFACTURER'S CONTROL DRAWING, CANADIAN ELECTRICAL CODE
4. BARRIERS MUST BE INSTALLED IN ACCORDANCE WITH BARRIER
3. MAY BE IN DIVISION 2 LOCATION IF SO APPROVED
2. INTERCONNECTING CABLE CAPACITANCE AND INDUCTANCE, PLUS
THE CAPACITANCE AND INDUCTANCE OF THE INTRINSICALLY SAFE
EQUIPMENT, MUST BE LESS THAN OR EQUAL TO THE CAPACITANCE
(Ca) AND INDUCTANCE(La) ENTITY PARAMETERS MARKED ON THE BARRIER.
CAPACITIANCE VALUE SHALL BE AS SHOWN IN TABLE 1.
NOT EXCEEDING Vmax AND Isc NOT EXCEEDING Imax
INTRINSICALLY SAFE FOR THE APPLICATION AND HAVE Voc
1. SELECTED BARRIERS MUST BE CERTIFIED AS
NOTES ON BARRIERS:
BARRIER
Voc
Isc
Ca
>
>
TABLE 1:
<
< La
1. ALL CABLE ENTRIES INTO THE ENCLOSURE MUST BE BROUGHT
THROUGH SUITABLY SIZED UL & CSA CERTIFIED LIQUID TIGHT
STRAIGHT THRU FITTINGS
5. WHEN SELECTING CABLE FOR CONNECTION TO
TURBINE METER, USE CABLE WITH THE FOLLOWING
HAZARDOUS LOCATION
REMOTE CABLE WITH STRAIGHT AMPHENOL
OPTIONAL CABLE ASSEMBLY
AMPHENOL CONNECTOR (PART #B220220)
REMOTE CABLE WITH 90° AMPHENOL
CONNECTOR (PART #B220221)
STRAIGHT. TO TURBINE
CONNECTOR 90° OR
OPTIONAL AMPHENOL
10 FT. TO MAX. 100 FT.
METER MOUNT OPTION
SWIVEL MOUNT OPTION
REMOTE MOUNT OPTION
WIRE HARNESS
PART #B300071
WIRE HARNESS
P0ART #B300070
HAZARDOUS LOCATION
(CLASSIFIED)
CLASS I, DIV 1
GROUP C & D
CLASS II, DIV 1
GROUP E, F & G
CLASS I, ZONE 0, IIB
NON-HAZARDOUS LOCATION
V Max
4-20mA Loop
I Max
Ci
Li
28 Vdc
26mA
0.5µF
0.0mH
Pulse Output Reset Input RS485
28 Vdc
100mA
0.0µF
0.0mH
5 Vdc
5mA
0.0µF
0.0mH
10 Vdc
60mA
0.0µF
0.0mH
* 0.1 mA @ .7 VOLT DROP
RTU/PLC
26 Vdc MAX.+
PULSE INPUT
-
GND.
MTL SAFETY BARRIER
TOTAL PULSE 1/F
1 3
2 4
SET POINT &
1 3
2 4
4-20mA 1/F
MODEL 7787+
MODEL 7706+
20-35 VDC
R LOAD
4-20mA
HOST
1 3
2 4
MODEL 7766 Pac
R5485 1/4
R5485
Turbine Input
Voc = 3.5V
Isc = 3.6mA
Ca = 15µF
La = 1.65H
1
1
21
TABLE 2
OTHER LOCAL CODES.
NOTES ON FLOW SENSOR
1. INTERCONNECTING CABLE CAPACITANCE AND INDUCTANCE, PLUS THE
CAPACITANCE AND INDUCTANCE OF THE MAGNETIC PICKUP, MUST BE LESS
THAN OR EQUAL TO THE CAPACITANCE(Ca) AND THE INDUCTANCE(La) "TURBINE
INPUT" ENTITY PARAMETERS MARKED ON THE B3000 MONITOR AND TABLE 2.
PARAMETERS: 0.2 uh/ft. AND 60 pF/ft.