Compact Digital Flow Monitor Model B3000 1 2 Menu Enter S1 S4 COM 1 MODEL SERIAL ! C 4-20mA Loop 28 Vdc 26mA 0.5µF 0.0mH MODEL SERIAL V Max I Max Ci Li ! Pulse Output Reset Input 28 Vdc 5 Vdc 100mA 5mA 0.0µF 0.0µF 0.0mH 0.0mH 1 12 US Electrical and Pulse Output Reset Input RS485 Turbine Input Hazardous 28 Vdc 5 Vdc 10 Vdc Voc=3.5V Location Safety 100mA 5mA 60mA Ics=3.6mA Intrinsically Safe When E113407 0.0µF 0.0µF 0.0µF Ca=1.5µF Installed Per Drawing Class I Div 1 Groups C,D 0.0mH 0.0mH 0.
Flow Monitor, B3000 Flow Monitor For Gas or Liquid Meters Page ii March 2014
Programming Manual CONTENTS INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 PART NUMBER CONSTRUCTION .
Flow Monitor, B3000 Flow Monitor For Gas or Liquid Meters MODBUS INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Modbus Register / Word Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Register Mappings . . . . .
Programming Manual March 2014 Page v
Compact Digital Flow Monitor, Model B3000 INTRODUCTION The B3000 flow monitor incorporates state-of-the-art, digital signal processing technology, designed to provide the user with exceptional flexibility at a very affordable price. Though designed for use with Blancett flow sensors, this monitor can be used with almost any flow sensor producing a low amplitude AC output or contact closure signal.
Programming Manual SPECIFICATIONS Display Common Simultaneously shows Rate and Total 5 x 7 Dot Matrix LCD, STN Fluid B30A/B/L/M/S 6 Digit Rate, 0.5 inch (12.7 mm) numeric 7 Digit Total, 0.5 inch (12.7 mm) numeric Engineering Unit Labels 0.34 inch (8.6 mm) B30W/X/Y/Z 6 Digit Rate, 0.37 inch (9.4 mm) numeric 7 Digit Total, 0.37 inch (13 mm) numeric Engineering Unit Labels 0.24 inch (6.
Compact Digital Flow Monitor, Model B3000 Status Alarms B30B/L/S/W/X None Modbus Digital Communications B30A/M/Y/Z B30B/L/S/W/X Modbus RTU over RS485, 127 addressable units / 2-wire network, 9600 baud, long integer and single precision IEEE754 formats; retrieve: flow rate, job totalizer, grand totalizer, alarm status and battery level; write: reset job totalizer, reset grand totalizer.
Programming Manual Response Time (Damping) Common Response Time 1…100 seconds response to a step change input, user adjustable Environmental Limits Common Limits –22…158° F (–30…70° C); 0…90% humidity, non-condensing; Materials and Enclosure Ratings B30A/B/L/M/S B30W/X/Y/Z Polycarbonate, stainless steel, polyurethane, thermoplastic elastomer, acrylic; NEMA 4X/IP 66 Copper free, epoxy-coated, aluminum, buna seal, NEMA 4X/IP66 Engineering Units Gallons, Liters, Oil Barrels (42 gallon), Liquid Barrels (3
Compact Digital Flow Monitor, Model B3000 INSTALLATION Connecting the B3000 to a Frequency Output Device Most turbine flow sensors produce a frequency output that is directly proportional to the volumetric flow through the sensor. There are, however, different output waveforms that can be presented to the display device depending on the transducer that converts the mechanical motion of the turbine into an electrical signal.
Programming Manual TR_B P1 TR_A RS485 Gnd Setpoint 2 Gnd Mag + Freq. In Pulse Mag JP1 Input JP1 Input – + JP1 Input Pulse Setpoint 1 Pulse Mag 4-20mA OC JP2 Total Pulse – + Iso Iso Total Pluse – JP2 JP3 Low High Low Signal Signal High Total Reset OC Total Pluse Input JP1 P1 P1 Signal Gnd Pulse Mag TB2 TB1 TB1 + Gnd Freq. In – Setpoint 2 + Setpoint 1 4-20mA – RS485 Gnd + TR_A Iso Total Pluse – TR_B Total Reset + – OC Total Pluse Signal Gnd 3.
Compact Digital Flow Monitor, Model B3000 POWER CONNECTIONS Standard The power supply used in the B30A/B/X/Z is an internal lithium 3.6V DC “D” cell that will power the monitor for about six years when no outputs are used. The monitor can also get power from a 4-20 mA current loop (see Figure 9 and Figure 10). If the current loop is used a sensing circuit within the monitor detects the presence of the current loop and disconnects the battery from the circuit.
Programming Manual Solar A solar cell mounted on the top of the monitor in the B30S charges an internal 3.6V DC nickel-cadmium battery that powers the monitor. A fully charged battery powers the monitor for approximately 30 days. The solar powered B3000 has a single totalizing pulse output and cannot be powered by a 4-20 mA loop.
Compact Digital Flow Monitor, Model B3000 OPERATING THE MONITOR The monitor has three modes of operation referred to as the Run, Programming, and Extended Programming modes. Communications Indicator Alarm Activation 1 Battery Indicator 2 Rate Rate Units Totalizer Multiplier Total Totalizer Units Figure 13: Display annunciators To access the program mode, momentarily press and then release MENU until the first programming screen is displayed.
Programming Manual Buttons MENU – Switches between normal running and programming modes. UP Arrow (▲) – In programming mode scrolls forward through the parameter choices and increments numeric variables. RIGHT Arrow (►) – In programming mode scrolls backward through the parameter choices and moves the active digit to the right. ENTER – Used to save programming information, advance to the next programming parameter, and in the reset process.
Compact Digital Flow Monitor, Model B3000 Programming Using Frequency Output Turbine Flow Meters Each Blancett turbine flow meter is shipped with either a K factor value or frequency data. If frequency data is provided, the data must be converted to a K factor before programming the monitor. K factor information, when supplied, can usually be found on the neck of the flow meter or stamped on the flow meter body.
Programming Manual PROGRAMMING PARAMETERS Conventions The individual programming parameters are arranged as follows. Top Line – Indicates what the parameter is and if it is a selection or an entry. Bottom Line – Indicates what menu level the parameter resides in. Select Fluid Type Fluid Basic Function At the Fluid prompt use ▲ or ► to select either Liquid or Gas. NNOTE: The fluid selection choice will affect what menu choices are available to the user.
Compact Digital Flow Monitor, Model B3000 1 2 Roll-Overs Roll-Over Indicator Total Totalizer Mode Figure 17: Grand total Test Test The Test setting places the monitor into a special diagnostic mode that shows the current input frequency and the accumulated input counts. Figure 18 shows the layout for test mode values. The diagnostic mode makes it possible for the user to see precisely the frequency input the monitor is seeing and is very useful in troubleshooting and noise detection.
Programming Manual Select Rate Units Setup Rate SU Extended Function The Rate SU is only available on the standard and solar liquid monitors. For the most basic unit setup choices the B3000 monitor has a simple and advanced setup option accessed through the rate setup parameter. If Simple is selected the rate and total choices are reduced to the five most common combinations avoiding the need to make unit and interval choices.
Compact Digital Flow Monitor, Model B3000 ENTER SPECIFIC GRAVITY VALUE (SPEC GR) Basic Function (activated when mass units are selected) The B3000 has two mass flow unit and two mass total unit choices (pounds and kilograms). When either pounds or kilograms are chosen in either the RateUnt or TotlUnt parameters the Spec Gr entry parameter is activated.
Programming Manual GAS COMPENSATION Gas Turbines Only Fluid measured by the gas turbine meter is compressible, and is also affected by temperature changes and pressure changes as illustrated by the ideal gas law equation. P1V1 P2V2 = T1 T2 Absolute Pressure and Temperature The ideal gas law equation shows that the volume of gas is determined by pressure and temperature applied to the gas under running conditions.
Compact Digital Flow Monitor, Model B3000 Totalizer Pulse Output PulsOut Basic Function The PulsOut parameter can be either enabled or disabled. When enabled, this output generates a fixed width 30 mS duration, pulse every time the least significant digit of the totalizer increments. The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a maximum 28V DC. The B3000 provides two types of totalizer pulses.
Programming Manual Flow at 20 mA Fl=20mA Basic Function When the display is operated using loop power, the flow rate that corresponds to 20 mA must be set. This setting normally represents the maximum rate of the flow sensor connected to the display but other entries are possible. At the Fl=20mA prompt, press ENTER. The current setting will begin to flash. If the current setting is correct, press ENTER to advance to the next parameter.
Compact Digital Flow Monitor, Model B3000 Linearization Linear Extended Function Enhanced accuracy can be obtained by linearization of the display. The linearization function accepts a maximum of ten points. Linearization requires additional calibration data from the meter to be used with the monitor. Typically, calibration information can be obtained in three, five, and ten points from the flow meter’s manufacturer. If linearization is not needed, press ► to advance to the next parameter.
Programming Manual Unit Under Test (UUT) Calibration Data Table In GPM UUT Frequency UUT Actual K factor (Hz x 60) Nominal K Hz Counts/Gallon GPM 50.02 755.900 906.72 28.12 426.000 15.80 8.88 Actual GPM 4.95 Linear Coefficient Raw Error 49.72 1.0060 0.59 908.96 28.02 1.0035 0.35 240.500 913.29 15.82 0.9987 -0.13 135.800 917.57 8.93 0.9941 -0.59 75.100 910.30 4.94 1.0020 0.20 Nominal K (NK) % Rate 912.
Compact Digital Flow Monitor, Model B3000 Set Point 1 SetPt 1 Extended Function The set point is the flow value at which the output transistor changes state. It is set using the same units as the rate units are entered. VCC 2.2…10K Pull-up Resistor 100 mA Maximum Open Collector Control Output 1 and 2 TR_B P1 P1 P1 TR_A TB1 VCC RS485 Gnd Gnd Setpoint 1 Setpoint 2 Setpoint 2 Setpoint 1 Gnd 100 mA Maximum 2.2…10K Pull-up Resistor RS485 Gnd + Freq.
Programming Manual Maximum Flow OF tp o Se ON FS et po in t in t Minimum Flow Output ON Output OFF Hysteresis Figure 26: Set point actions NNOTE: Neither the set point nor the hysteresis values are checked against the meter size to see if they are appropriate. Care should be used when entering these values, especially in critical applications, as it is possible to enter inappropriate values preventing the outputs from working as expected.
Compact Digital Flow Monitor, Model B3000 Clear Grand Total CLR G-T Basic Function At the Clr G-T prompt, press ENTER. The display will now say no on the screen. To clear the grand total press either ▲ or the ► to change from no to yes. Press ENTER to select yes and advance to the next parameter. The totalizer can also be reset using a hardware reset as shown in the following diagrams. Input JP1 TR_B Pulse Mag P1TR_A TB2 + RS485 Gnd Freq. In Setpoint 1 – Setpoint 2 + 4-20mA Gnd – + Freq.
APPENDIX Programming Manual TROUBLESHOOTING GUIDE Trouble No LCD Display Remedy Battery – B30A/B/X/Z only Check battery voltage. Should be 3.6V DC. Replace if low or bad. Loop Power NNOTE: Not available on B30S Check 4-20 mA input. Voltage must be within the minimum and maximum supply voltage and capable of supplying enough current to run the display. The input voltage is checked “across” or in parallel with the 4-20 mA terminals.
Compact Digital Flow Monitor, Model B3000 Battery Replacement (B30A/B/X/Z only) Battery powered monitors use a single 3.6V DC “D” size, lithium battery. When replacement is necessary, use a clean fresh battery to ensure continued trouble-free operation. Replacement Batteries Manufacturer Part Number Blancett B300028 Xeno S11-0205-10-03 Tadiran TL-5930/F Table 6: Replacement batteries NEMA 4X Enclosure Unscrew the four captive screws on the front panel to gain access to the battery.
Programming Manual 5. 6. 7. 8. Cut the tie wrap holding the battery to the mounting plate and remove the worn-out battery. Install a new tie wrap and battery securing the battery to the mounting plate with the tie wrap. Re-install the battery mounting plate. Plug the battery into the circuit board and re-install the circuit assembly into the explosion proof housing using the thumb screws. 9. Re-install the enclosure screw cover. Thumb Screws Menu Battery Bracket Tie Wrap Enter S1 S4 3.
Page 32 Numeric Entry K-Factor Value KFactor Pulses/Gallon Pulses/M³ Pulses/Liter Pulses/Ft³ K-Factor Unit KFacUnt Flow Flow-GT Test Display Options Display 0375 0500 0750 0875 1.0 1.5 2.0 3.0 4.0 6.0 8.0 10.
March 2014 Numeric Entry K-Factor Value KFactor Pulses/Gallon Pulses/M³ Pulses/Liter Pulses/Ft³ K-Factor Unit KFacUnt Flow Flow-GT Test Display Options Display 0375 0500 0750 0875 1.0 1.5 2.0 3.0 4.0 6.0 8.0 10.
Page 34 Numeric Entry K-Factor Value KFactor Pulses/Gallon Pulses/M³ Pulses/Liter Pulses/Ft³ K-Factor Unit KFacUnt Flow Flow-GT Test Display Options Display 0375 0500 0750 0875 1.0 1.5 2.0 3.0 4.0 6.0 8.0 10.
March 2014 Numeric Entry K-Factor Value KFactor Pulses/M³ Pulses/Liter Pulses/Ft³ K-Factor Unit KFacUnt Flow Flow-GT Test Display Options Display 2” Low 2” Medium 2” High Meter Size/Capacity Meter Liquid Gas Fluid Type Fluid START Totalizer Multiplier x1000 x100 x10 (T) (T) (T) (T) (T) (T) (T) Low Flow Cutoff Operating Pressure in PSI Damping Numeric Entry Flow at 20 mA Fl=20mA Disabled Enabled PulsOut Pulse Output Numeric Entry Display Damping Linear Points (2 to10) Linear Li
Page 36 Numeric Entry K-Factor Value KFactor Pulses/M³ Pulses/Liter Pulses/Ft³ K-Factor Unit KFacUnt Flow Flow-GT Test Display Options Display 2” Low 2” Medium 2” High Meter Size/Capacity Meter Liquid Gas Fluid Type Fluid START Rate Unit / Time Totalizer Multiplier X 1,000 X 100 X 10 X1 X 0.1 X 0.
March 2014 Numeric Entry K-Factor Value KFactor Pulses/M³ Pulses/Liter Pulses/Ft³ K-Factor Unit KFacUnt Flow Flow-GT Test Display Options Display 2” Low 2” Medium 2” High Meter Size/Capacity Meter Liquid Gas Fluid Type Fluid START Totalizer Multiplier x1000 x100 x10 (T) (T) (T) (T) (T) (T) (T) Low Flow Cutoff Operating Pressure in PSI Disabled Enabled PulsOut Pulse Output Numeric Entry Display Damping Damping Linear Points (2 to10) Linearization Linear Numeric Entry Coef#(x) C
Compact Digital Flow Monitor, Model B3000 K FACTORS EXPLAINED The K factor (with regards to flow) is the number of pulses that must be accumulated to equal a particular volume of fluid. You can think of each pulse as representing a small fraction of the totalizing unit. An example might be a K factor of 1000 (pulses per gallon). This means that if you were counting pulses, when the count total reached 1000, you would have accumulated one gallon of liquid.
Programming Manual Example 3 Known values are: Velocity = Inside Diameter of Pipe = 4.3 ft/sec 3.068 in. Find the area of the pipe cross section. Area = πr2 2 3.068 2 Area = π = π x 2.35 = 7.39 in 2 Find the volume in one foot of travel. 7.39 in2 x 12 in. (1 ft) = 88.71in2 ft What portion of a gallon does one foot of travel represent? 88.71 in3 231 in3 = 0.384 gallons So for every foot of fluid travel 0.384 gallons will pass. What is the flow rate in gpm at 4.3 ft/sec? 0.
Compact Digital Flow Monitor, Model B3000 Declaration of Conformity ® Badger Meter We: of: Badger Meter, Inc. 4545 W. Brown Deer Road Milwaukee, WI 53224 USA EU Representative: of: Badger Meter, Europa Nürtingerstr.
Programming Manual SYMBOL EXPLANATIONS CAUTION REFER TO ACCOMPANYING DOCUMENTS. WARNING EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2. AVERTISSMENT RISQUE D’EXPLOSION - LA SUBSTITUTION DE COMPOSANTS PEUT RENDRE CEMATÉRIEL INACCCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2. WARNING DO NOT CONNECT OR DISCONNECT EITHER POWER OR OUTPUTS UNLESS THE AREA IS KNOWN TO BE NON-HAZARDOUS. AVERTISSMENT RISQUE D’EXPLOSION.
Compact Digital Flow Monitor, Model B3000 EXPLOSION-PROOF ENCLOSURE The ExDirect instrument enclosure is designed to house instrumentation and control equipment as well as act as a conduit. Installation 1. ExDirect instrument enclosures are furnished with three 3/4 in. NPT offset through-feed cast hubs for conduit entries. 2. Secure the enclosure to the conduit system.
Programming Manual WARNING THE HAZARDOUS LOCATION INFORMATION SPECIFYING CLASS AND GROUP LISTING OF EACH INSTRUMENT ENCLOSURE IS MARKED ON THE NAMEPLATE OF EACH ENCLOSURE. CAUTION ALL UNUSED CONDUIT OPENINGS MUST BE PLUGGED. PLUG UNUSED CONDUIT OPENINGS WITH APPROVED EXPLOSION PROOF PLUGS. PLUGS MUST BE A MINIMUM OF 1/8"THICK AND ENGAGE A MINIMUM OF 5 FULL THREADS.
A B C D E F G H 11 R LOAD 4-20mA HOST 2 1 MTL SAFETY BARRIER MODEL 7787+ 2 1 MODEL 7766 Pac MODEL 7706+ * 0.1 mA @ .7 VOLT DROP 2 1 12 NOTES: UNLESS OTHERWISE SPECIFIED 3. RADII TO BE .005/.010 2. FINISH TO BE 63 1. REMOVE ALL BURRS AND BREAK SHARP EDGES .005/.010 R5485 20-35 VDC - Pulse Output 28 Vdc 100mA 0.0µF 0.0mH 4 3 4 3 4 3 11 NON-HAZARDOUS LOCATION 4-20mA Loop 28 Vdc 26mA 0.5µF 0.0mH GND. PULSE INPUT 26 Vdc MAX.
Programming Manual MODBUS INTERFACE A subset of the standard Modbus commands is implemented to provide access into the data and status of the B3000 Monitor. This feature is available on the B3000 Advanced models only.
Compact Digital Flow Monitor, Model B3000 Register Mappings MODBUS Registers Data Component Name Long Integer Format Single Precision Floating Point Format Available Units Spare 40100…40101 40200…40201 – Flow Rate 40102…40103 40202…40203 Spare 40104…40105 40204…40205 Positive Totalizer 40106…40107 40206…40207 Grand Total Totalizer 40108…40109 40208…40209 Gallons, Liters, MGallons, Cubic Feet, Cubic Meters, Acre Feet, Oil Barrel, Liquid Barrel, Feet, Meters, Lb, Kg, BTU, MBTU, MMBTU, TON
Programming Manual Modbus Coil Description Modbus Coil Notes Reset Running Totalizer 1 Forcing this coil ON will reset the running totalizer. After reset, the coil automatically returns to the OFF state. Reset Grand Totalizer 2 Forcing this coil ON will reset both the running totalizer and the grand totalizer. After reset, the coil automatically returns to the OFF state.
Compact Digital Flow Monitor, Model B3000 C Source Code A.1.
Programming Manual WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT (WEEE) DIRECTIVE In the European Union, this label indicates that t his product should not be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling. For information on how to recycle this product responsibly in your country, please visit: www.badgermeter.
Compact Digital Flow Monitor, Model B3000 INTENTIONAL BLANK PAGE Page 50 March 2014
Programming Manual INTENTIONAL BLANK PAGE March 2014 Page 51
Control. Manage. Optimize. Blancett is a registered trademarks of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. © 2014 Badger Meter, Inc. All rights reserved. www.badgermeter.