Flow Monitor B2800 Flow Monitor – Simplified DSY-PM-00276-EN-01 (November 2013) Programming Manual
Flow Monitor, B2800 Flow Monitor – Simplified Page ii November 2013
Programming Manual CONTENTS INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 OPERATING THE MONITOR . .
Flow Monitor, B2800 Flow Monitor – Simplified Page iv November 2013
Programming Manual INTRODUCTION The B2800 Flow monitor is a state-of-the-art digital signal processing flow monitor, designed to provide the user with exceptional flexibility at a very affordable price. Though designed for use with Blancett flow meters, this display can be used with almost any flow meter producing a low amplitude AC output or contact closure signal(s). This flow monitor is capable of accepting a low level frequency input for calculating flow rate and total.
Flow Monitor, B2800 Flow Monitor – Simplified SPECIFICATIONS Power Supply Options Battery Powered One D size, 1.5V alkaline battery. Loop Powered Optional 4-20 mA loop power. Alphanumeric Rate and Total Display Eight digit, 0.75 inch high numeric display. Eight character, 0.38 inch high alphanumeric display. Fixed or toggle modes of operation for flow rate and totalizer display. Accuracy ±0.1%. Temperature Drift 50 ppm / °C (maximum). Mounting Classification Meter Mount Type 4X enclosure.
Programming Manual BASIC PROGRAMMING Keys MENU – Switches to PROGRAM mode UP Arrow – Scrolls forward through the parameter choices and increments numeric variables RIGHT Arrow – Scrolls backward through the parameter choices and moves the active digit to the right ENTER – Used to save programming information, advance to the next programming parameter, and in the reset process Modes RUN – Normal operating mode PROGRAM – Used to program variables into the display If your monitor was ordered with a Blancett
Flow Monitor, B2800 Flow Monitor – Simplified Select Meter Size At the METER prompt, press the UP or RIGHT arrows to select the bore size of your meter. Press ENTER to save meter size choice and advance to the K factor units selection. NNOTE: The meter connection size and the bore size are different. For example, many of the one inch NPT turbines have bore sizes that range from 3⁄8 inch up to 1 inch. Be sure to use the correct bore size or the meter will report incorrect flows and totals.
Programming Manual Password Password protection prevents unauthorized users from changing programming information. Initially, the password is set to all zeros. To change the password, simply enter any four digit code using the arrow keys as previously described to enter the password value. Pressing ENTER once will store the password and take you back to the RST PSWD screen. NNOTE: This password will allow the operator to manually reset totals.
Flow Monitor, B2800 Flow Monitor – Simplified Pulse Input Card 30V DC (Max) 1 10K + 20 mS Pulse 2 3 4 5 6 - + - + - + Pulse In - Pulse In Magnetic Pickup Analog Input Card - 4-20 mA RMAX = 10…30V DC (Loop Supply Voltage - 5) 0.
Programming Manual TROUBLESHOOTING GUIDE Trouble Remedy No LCD Display • Check battery voltage. Should be 1.5V DC. Replace if low or bad. No Rate or Total Displayed • Check connection from meter pickup to display input terminals. • Check turbine meter rotor for debris. Rotor should spin freely. • Check programming of flow monitor. Flow Rate Display Interprets Reading Constantly • • • • Flow Rate Indicator Bounces • This usually indicates a weak signal. Replace pickup and/or check all connections.
Page 12 RST PSWD PASSWORD PULS ON PULS OFF TEST BPD/BBL PUL/FT3 M3PD/M3 PUL/LTR RATE M3PH/M3 TOTAL Pulse Output LPM/LIT BOTH GPM/GAL PUL/GAL PUL/M3 DSP Units K FACTOR K Factor Units METER IO/SETUP Flow Monitor, B2800 Flow Monitor – Simplified Figure 5: Basic programming menu November 2013
Programming Manual ADDITIONAL SCALING PARAMETERS NNOTE: The programming instructions below are only available for loop powered units. Battery powered units will not see these programming choices. B2800 Simplified 4-20 mA Programming Instructions FLOW 4 mA Setting When the loop powered option is ordered, the flow rate that corresponds to 4 mA must be set. Zero is default flow rate for this setting. If the current selection is correct, press ENTER once to advance to the next parameter.
Flow Monitor, B2800 Flow Monitor – Simplified Mag Input 2J Keypad Connector JP2 1 2 3 4 5 DC 1 2 + Out Pulse 3 Pulse Inuput 4 5 6 + mA4-20 + - TB1 Freq.
November 2013 A B C D E F G H 12 12 11 11 10 10 9 9 8 8 7 7 6 6 5 5 4 4 3 3 2 D 2 59380 1 B280001 1 A B C D E F G H Programming Manual Page 15 B280001
PART NUMBERING INFORMATION B 28 S X X - X X Units of Measure AB - Gallons ED - Barrels HB - Liters ID - Cubic Meters Program Level S - Simplified Power Option B - Battery L - Loop Mounting Style M R S H - Meter Mount Remote Mount Swivel Mount Hand-Held REPLACEMENT PARTS Component Part Number Keypad B260713 Battery B280601 Battery Tie Wrap B228036 Pickup Cable B222-121 Desiccant Bag B260630 PVC Union B220016 PVC Reducer Bushing B220056 Rubber Washer B228207 Steel Lock Washer B220018