Enter the Meter's K Factor
To change the K-FACTOR value, use the RIGHT arrow and select the position of the number that you wish to change. Using
the UP arrow, increment the display digit until it matches the meter’s Kfactor digit. Repeat this process until all K factor digits
have been entered. Press ENTER to save the K factor and advance to the RATE/TOTAL units selection.
Select the Rate/Total Units of Measure
The monitor allows the choice of five common rate/total units. The monitor shows the rate/total unit that the display is
currently set for. If the current selection is correct, press ENTER to advance to the next parameter. To change to an alternate
unit, use the arrow keys to scroll to the desired rate unit and press ENTER to save the choice.
Selection Rate Total
GPM/GAL Gallons per minute Gallons
LPM/LIT Liters per minute Liters
M3PH/M3 Cubic meters per hour Cubic meters
M3PD/M3 Cubic meters per day Cubic meters
BPD/BBL Oil barrels per day Oil barrels
OTE:N The total unit’s output multiplier cannot be modified in the Simplified program level. This option is reserved in the
Advanced program level.
Select the Display Function
The monitor can display RATE or TOTAL or alternate between BOTH rate and total. If the current selection is correct, press
ENTER to advance to the next parameter. To change to an alternate display mode, use the arrow keys to scroll to the desired
display mode and press ENTER to save the choice.
A TEST function is also available in the display function submenu. With the test function selected, the display acts like a
frequency counter and displays the raw input frequency being supplied to the frequency input terminals. This is very useful
when troubleshooting flow problems.
Totalizer Pulse Output
The pulse output parameter can be either enabled or disabled. When enabled this output generates 20 mS duration pulse for
every time the least significant digit of the totalizer increments. The amplitude of the pulse is dependent on the voltage level
of the supply connected to the pulse output and is limited to a maximum 30V DC.
Password
Password protection prevents unauthorized users from changing programming information. Initially, the password is set to
all zeros. To change the password, simply enter any four digit code using the arrow keys as previously described to enter the
password value. Pressing ENTER will store the password and take you back to the RST PSWD screen.
OTE:N This password will allow the operator to manually reset totals.
Reset Password
The reset password screen allows the operator to enter any four digit code for the manual reset totals function.
OTE:N This reset password code will not allow the operator to enter the PROGRAM mode.
Reset Total
To reset the monitor total display, in RUN mode press MENU and ENTER simultaneously until TOTAL RST starts to flash. The
TOTAL RST will stop flashing and the display will return to the RUN mode at the conclusion of the reset procedure.
Store Total
The current total can be manually stored in the monitor’s flash memory. This procedure may be desirable prior to replacing
the battery. Press and hold ENTER for two seconds. The display will respond with a flashing TOTALSVD and then return to the
RUN mode.