Flow Monitor B2800XP Explosion Proof Monitor – Simplified DSY-PM-00277-EN-01 (November 2013) Programming Manual
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified Page ii November 2013
Programming Manual CONTENTS INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 EXPLOSION PROOF ENCLOSURE .
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Manual INTRODUCTION The B2800XP flow monitor is a state-of-the-art digital signal processing flow monitor designed to provide the user with exceptional flexibility at a very affordable price. Though designed for use with Blancett flow meters, this display can be used with almost any flow meter producing a low amplitude AC output or contact closure signals. The B2800XP flow monitor is capable of accepting a low level frequency input for calculating flow rate and total.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified SPECIFICATIONS Power Supply Options Battery Powered One D size, 1.5V alkaline battery. Loop Powered 4-20 mA loop power. Power Consumption Battery Powered Less than 1 mA @ 1.5V DC. Loop Powered 25 mA (maximum). Alphanumeric Rate and Total Display Eight digit, 0.5 inch high numeric display. Eight character, 0.25 inch high alphanumeric display.
Programming Manual EXPLOSION PROOF ENCLOSURE The EIH Instrument enclosure is designed to house instrumentation and control equipment as well as act as a conduit outlet body in hazardous, abusive and wet locations. The EIH enclosure is approved by Underwriters Laboratories Inc.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified USE CARE TO PREVENT DIRT, GRIT OR OTHER FOREIGN MATERIAL FROM LODGING ON THREADS. IF SUCH MATERIAL SETTLES ON THREADS, CLEAN WITH KEROSENE OR STODDARD SOLVENT*, THEN RE-LUBRICATE WITH COOPER CROUSE-HINDS TYPE STL THREAD LUBRICANT. 8. Tighten cover set screws to prevent cover from loosening under vibration. * TO AVOID THE POSSIBILITY OF AN EXPLOSION, OXIDATION AND CORROSION, DO NOT USE GASOLINE OR SIMILAR SOLVENT.
Programming Manual INSTALLATION KITS To facilitate installation of the explosion proof B2800XP monitor two sizes of installation kits are available. Hub Size Kit Number Meter Sizes 1/2 in. NPT Hub B280-742 3/8 in., 1/2 in., 3/4 in. with 1/2 in. NPT End Fittings 1 in. NPT Hub B280-737 All Sizes with 1 in.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified PROGRAMMING The monitor has two modes of operation referred to as the RUN mode and the PROGRAM mode. Both the RUN mode and the PROGRAM mode display screen enunciators confirm the state of the monitor. A quick glance at the lower left-hand corner of the LCD screen will confirm operating status. Normal operation will be in the RUN mode. To access the PROGRAM mode, press MENU until the first programming screen is displayed.
Programming Manual At the METER prompt, press UP or RIGHT arrows to select the bore size of your meter. Press ENTER to save meter size choice and advance to the K factor units selection. NNOTE: The meter connection size and the bore size are different. For example, many of the 1 inch NPT turbines have bore sizes that range from 3⁄8 inch up to 1 inch Be sure to use the correct bore size or the meter could report incorrect flows and totals.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified Reset Password Reset password protection prevents unauthorized users from manually resetting the flow monitor’s accumulated totals. Initially, the password is set to all zeros. To change the reset password, simply enter any four digit code using the arrows as previously described to enter the password value. Pressing ENTER will store the reset password.
Programming Manual D 1.5 VOLTS CAUTION DO NOT CONNECT IMPROPERLY CHANGE OR DISPOSE OF IN FIRE. BATTERY MAY EXPLODE OR LEAK. MADE IN U.S.A. ALKALINE BATTERY External Totalizer Reset External Totalizer Reset TB2 Reset Pulse Inuput TB2 Reset + - Pulse Out Pulse Inuput + - Pulse Out Freq. In + - + - 4-20 mA Mag Input + - + - 4-20 mA 30V DC (Max) Freq.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified ADDITIONAL SCALING PARAMETERS NNOTE: The programming instructions below are only available for loop powered models. Battery powered models will not include these programming choices. NNOTE: If the B2800XP flow monitor was ordered with a Blancett turbine flow meter, the 4…20 mA was programmed and factory calibrated.
Programming Manual mA DC % 0 MEM MANUAL AutoHOLD FAST MIN MX HOLD MIN MAX LOGGING CANCEL SAVE Hz % ms RANGE SETUP YES REL TB2 Reset 0 NO Pulse Inuput nS mV W ac+dc °F °C V ac+dc + - A mA Pulse Out mV µA V A mA dB dB Freq.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified METER IO/SETUP K Factor Units PUL/GAL PUL/M3 LPM/LIT M3PH/M3 PUL/LTR PUL/FT3 K FACTOR Units GPM/GAL DSP BOTH Pulse Output PULS ON TOTAL RATE M3PD/M3 BPD/BBL TEST PULS OFF PASSWORD RST PSWD Figure 6: Basic programming menu IO/SETUP DSP PULSE OUTPUT Flow 4MA Flow 20MA 4MA OUT 20MA OUT 4-20 TEST PASSWORD Figure 7: 4-20 mA programming menu Page 16 November 2013
Programming Manual TROUBLESHOOTING GUIDE Trouble No LCD Display Remedy • Battery Powered Version: Check battery voltage. Should be 1.5V DC. Replace if low or bad. • Loop Powered Version: Check for current flow in the loop. Check polarity of the current loop connections for proper orientation. • • • • Check connection from meter pickup to display input terminals. Check turbine meter rotor for debris. Rotor should spin freely. Check programming of flow monitor.
Flow Monitor, B2800XP Explosion Proof Monitor – Simplified DIMENSIONS 5.25" 5 16 5.10" MENU ENTER 2.60" 4.
Programming Manual PART NUMBER INFORMATION B 28 S X X - X X Units of Measure AB - Gallons ED - Barrels HB - Liters ID - Cubic Meters Program Level S - Simplified Power Option B - Battery L - Loop Mounting Style X - Explosion proof REPLACEMENT PARTS Component November 2013 Part Number Enclosure B280635 Battery B280601 Battery Holder B280634 Battery Tie Wrap B228036 Cap Plug 3/8 inch B118236 Desiccant Pouch B220141 Pickup Cable B222-121 Battery Mount Plate B280618 Adapter Bridge Plate
Blancett is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding contractual obligation exists. © 2013 Badger Meter, Inc. All rights reserved. www.badgermeter.