User Manual
INSTALLATION
1. Cut a 3.6 inch × 3.6 inch square opening in the panel. See Figure 2.
2. Disconnect the battery from the main board terminal.
3. Remove the large battery mounting plate by removing the four Phillips head screws from the main assembly standos.
4. Mount the main assembly through the panel opening and temporarily hold in place (tape will work).
5. Attach the signal wires to the appropriate terminal blocks.
6. Reattach the large battery mounting plate with the four Phillips head screws.
7. Secure the assembly to the panel with the four outer screws.
3.6 in
(9.144 cm)
3.6 in
(9.144 cm)
Figure 2: Panel cutout
OPERATING THE MONITOR
The monitor has two modes of operation referred to as the RUN mode and the PROGRAM mode. Both the RUN mode and the
PROGRAM mode display screen enunciators confirming the state of the monitor. A quick glance at the lower left-hand corner
of the LCD screen will confirm operating status. Normal operation will be in the RUN mode. To access the PROGRAM mode,
press MENU until the first programming screen is displayed. After programming the display with the necessary information, a
lock out feature can be turned on to prevent unauthorized access or changing the meter’s setup parameters.
BASIC PROGRAMMING MODE
Keys
MENU – Switches to PROGRAM mode
UP Arrow – Scrolls forward through the parameter choices and increments numeric variables
RIGHT Arrow – Scrolls backward through the parameter choices and moves the active digit to the right
ENTER – Used to save programming information, advance to the next programming parameter, and in the reset process
Modes
RUN – Normal operating mode
PROGRAM – Used to program variables into the display
If your monitor was ordered with a Blancett flow meter, the two components ship from the factory calibrated as a set. If the
monitor is a replacement, the turbine’s K factor has changed, or the monitor is being used with some other pulse generating
device, programming will be necessary.
Programming Manual