User Manual

TROUBLESHOOTING GUIDE
Trouble Remedy
No LCD Display Check battery voltage. Should be 1.5V DC. Replace if low or bad.
No Rate or Total
Displayed
Check connection from meter pickup to display input terminals.
Check turbine meter rotor for debris. Rotor should spin freely.
Check programming of flow monitor.
Flow Rate Display
Interprets Reading
Constantly
This is usually an indication of external noise. Keep all AC wires separate from DC wires.
Check for large motors close to the meter pickup.
Check for radio antenna in close proximity.
Try disconnecting the pickup from the monitor pig tail. This should stop the noise. If not, then try
reorientating the meter to a new location.
Flow Rate Indicator
Bounces
This usually indicates a weak signal. Replace pickup and/or check all connections.
Examine K factor.
DEFAULT K FACTOR VALUES
Meter Size Default K factor Lower Limit Upper Limit
38 in. 20,000 16,000 24,000
1/2 in. 13,000 10,400 15,600
3/4 in. 2750 2200 3300
7⁄8 in. 2686 2148 3223
1 in. 870.0 696.0 1044
1-1/2 in. 330.0 264.0 396.0
2 in. 52.0 41.6 62.0
3 in. 57.0 45.6 68.0
4 in. 29.0 23.2 35.0
6 in. 7.0 5.6 8.0
8 in. 3.0 2.4 4.0
10 in. 1.6 1.3 2.0
Flow Monitor, B2800 Panel Mount – Advanced
Page 18 November 2013