Owner manual

7500S MAG METER STANDARD SWITCH SETTINGS
½" Meter (1-30 gpm) Pre Selection Factor Jumper Position
1 Pulse Per Gallon 1500 D
10 Pulse Per Gallon 1500 D
100 Pulse Per Gallon 0150 D
500 Pulse Per Gallon 0030 D
1 Pulse Per Liter 3965 D
1" Meter (3-80 gpm)
1 Pulse Per Gallon 6000 D
10 Pulse Per Gallon 0600 D
100 Pulse Per Gallon 0060 D
500 Pulse Per Gallon 0012 D
1 Pulse Per Liter 1585 D
2" Meter (10-315 gpm)
1 Pulse Per Gallon 0750 C
10 Pulse Per Gallon 0075 C
1 Pulse Per Liter 0075 C
3" Meter (24-690 gpm)
1 Pulse Per Gallon 0380 B
10 Pulse Per Gallon 0038 B
1 Pulse Per Liter 0038 B
4" Meter (40-1200 gpm)
1 Pulse Per Gallon 0250 A
10 Pulse Per Gallon 0025 A
1 Pulse Per Liter 0025 A
PRE-SELECTION SWITCHES
On the board diagram on the previous page, note the
position of the (4) "Pre-Selection Rotary Switches." As
per the above chart, these switches are set at the
factory per meter size and general magnitude of pulse
output desired. If a change of resolution (pulse output
value) is required, change the Pre-Selection Switches
to above values.
7
Example:
Setting of Pre-
selection Rotary
Switch Settings
3" Meter with
1 pulse/gallon = 0380
1 0
10 8
100
3
1000 0
JUMPER LOCATION
Please note the jumper area in the illustration. There
are (4) jumper positions designated by A, B, C, and D.
The jumper must be located in the correct position
for the respective meter size.