7500P MAG METER STANDARD SWITCH SETTINGS
½" Meter (1-30 gpm) Pre Selection Factor Jumper Position
1 Pulse Per Gallon 1500 D
10 Pulse Per Gallon 1500 D
100 Pulse Per Gallon 0150 D
500 Pulse Per Gallon 0030 D
1 Pulse Per Liter 3965 D
1" Meter (3-80 gpm)
1 Pulse Per Gallon 6000 D
10 Pulse Per Gallon 0600 D
100 Pulse Per Gallon 0060 D
500 Pulse Per Gallon 0012 D
1 Pulse Per Liter 1585 D
2" Meter (10-315 gpm)
1 Pulse Per Gallon 0750 C
10 Pulse Per Gallon 0075 C
1 Pulse Per Liter 0075 C
3" Meter (24-690 gpm)
1 Pulse Per Gallon 0380 B
10 Pulse Per Gallon 0038 B
1 Pulse Per Liter 0038 B
4" Meter (40-1200 gpm)
1 Pulse Per Gallon 0250 A
10 Pulse Per Gallon 0025 A
1 Pulse Per Liter 0025 A
PRE-SELECTION SWITCHES
On the board diagram on the previous page, note the po-
sition of the (4) "Pre-Selection Rotary Switches." As per
the above chart, these switches are set at the factory per
meter size and general magnitude of pulse output desired.
If a change of resolution (pulse output value) is required,
change the Pre-Selection Switches to above values.
7
Example:
Setting of Pre-
selection Rotary
Switch Settings
3" Meter with
1 pulse/gallon = 0380
1��
0
10��
8
100�� 3
1000�
0
JUMPERLOCATION
Please note in the illustration the jumper area. There are
(4) jumper positions designated by A, B, C, and D. The
jumper must be located in the correct position for the
respective meter size. The "D" position is for 1/2" and
1" meters. The A, B, and C positions are for 4", 3" and 2"
sizes respectively. See chart above.