Instruction Manual

Page 10
7-11
Series 380 Impeller Btu System
Series 380 BACnet Object Map
Description ID Name Units
Analog Input AN1 TempIn ºC, ºF
Analog Input AN2 TempOut ºC, ºF
Analog Value AV1 VolFlow
gpm, gph, lpm, lps, lph,
ft
3
/s, ft
3
/m, ft
3
/h, m
3
/s,
m
3
/min, m
3
/h, custom
Analog Value AV2 EnergyFlow
kBtu/min, kBtu/h, kW,
MW, HP, Tons, custom
Analog Value AV3 TotalVol
gallons, galx100,
galx1000, liters, ft
3
, m
3
,
custom
Analog Value AV4 TotEnergy
Btu, kBtu, MBtu, kWh,
MWh, kJ, MJ, custom
Analog Value AV5 TempMode dimensionless
Analog Value AV6 FFilterCoef dimensionless
Analog Value AV7 TFiltCoef dimensionless
Analog Value AV8 SpHtCapac Btu/lb-F
Analog Value AV9 Density lb/gallon
Analog Value AV10 SerialNum dimensionless
BACnet Protocol Implementation Conformance Statement
BMA Doc. x – 00x Page 1 of 1
BACnet Standardized Device Profile
Device Profile Tested
BACnet Smart Actuator (B-SA)
Supported BIBBs
Supported BIBBs BIBB Name Tested
DS-RP-B ReadProperty - B
DS-WP-B WriteProperty - B
DM-DDB-B
Dynamic Device Binding - B (Who-Is, I-Am)
Standard Object Types Supported
Object Type Creatable Deletable Tested
Analog Input No No
Analog Value No No
Device No No
Data Link Layer Options
Data Link Options Tested
MS/TP Slave
baud rates: 9600, 19200,
38400, 76800 bps
Segmentation Capability
Segmentation Type Supported
Window Size
(MS/TP product limited to 1)
Tested
Able to transmit segmented messages No N/A
Device Address Binding
Static Binding Supported Tested
No N/A
Character Sets
Character Sets supported Tested
ANSI X3.4
Figure 6: BACnet Device Profile