Instruction Manual
5
Sensor Wiring
All flow sensor types connect to the four terminal
header labeled “sensor input”.
Series 200
Connect the red wire to sensor signal (+), black wire
to sensor signal (-) and the bare wire to shield.
SDI Series
Connect the plus (+) terminal of the sensor to
sensor signal (+) on the transmitter and the minus
(-) terminal of the sensor to sensor signal (-) on the
transmitter. Connect the shield terminal of the sensor
to the shield terminal of the transmitter.
Other Sensors
The sensor input Power Out terminal supplies
nominal 12VDC excitation voltage for 3 wire sensors.
Connect sensor signal + and sensor signal - wires to transmitter terminals.
Temperature Element Wiring
The Badger Meter thermistors are not polarity sensitive.
Connect thermistor closest to the flow sensor to Series 340
terminal block marked TEMP 1 and the other thermistor wires to
Series 340 terminal marked TEMP 2.
Connecting the L
ONWORKS
®
Bus
The LONWORKS network connection is not polarity sensitive.
Refer to”commissioning” section
10KΩ Thermistors
Supply
Return
Thermistor Wiring Diagram
To O N OR KS
Network
LW
®
Not Polarity
Sensitive
Red
Black
Shield
(if applicable)
Series 200
or
SDI
Sample Sensor Wiring Diagram