Energy Transmitter Owner's manual
RS-485 Network Configuration – BACnet
Figure 30: BACnet Option
Select BACnet to access the BACnet pull down menus.
Select the Bit Rate (BAUD rate) to match other devices on the network.
BACnet Device Name can be set to help identify this device and location.
BACnet Device ID (Incidence #) is a unique number that identifies this device on the network. Typically, the first part of the
number is the same as the network #, and the last two characters are the same as the Address.
NOT:N This is not a requirement, but can help in system planning.
BACnet Object Map
Description ID Name
Out of
Service
Units
Analog Input AN1 TempIn FALSE º C, º F
Analog Input AN2 TempOut FALSE º C, º F
Analog Input AN3 FreqIn FALSE Hz
Analog Input AN4 VolFlow FALSE
gpm, gph, lpm, lph,
ft
3
/s, ft
3
/m, ft
3
/h, m
3
/s,
m
3
/min, m
3
/h
Analog Input AN5 EnrgyFlow FALSE
kBtu/min, kBtu/h, kW,
MW, HP, Tons
Analog Value AV1 TotalVol FALSE gallons, liters, ft
3
, m
3
Analog Value AV2 TotEnergy FALSE
Btu, kBtu, MBtu, kWh,
MWh, kJ, MJ
Analog Value AV3 Kfactor FALSE dimensionless
Analog Value AV4 Offset FALSE dimensionless
Analog Value AV5 TempMode FALSE dimensionless
Analog Value AV6 FFilterCoef FALSE dimensionless
Analog Value AV7 TFiltCoef FALSE dimensionless
Analog Value AV8 SpHtCapac FALSE Btu/lb-F
Analog Value AV9 Density FALSE lb/gallon
Analog Value AV10 InTACoef FALSE dimensionless
Analog Value AV11 InTBCoef FALSE dimensionless
Analog Value AV12 InTCCoef FALSE dimensionless
Analog Value AV13 InTOffset FALSE º C, º F
Analog Value AV14 OutTACoef FALSE dimensionless
Analog Value AV15 OuTBCoef FALSE dimensionless
Analog Value AV16 OutTCCoef FALSE dimensionless
Analog Value AV17 OutTOffset FALSE º C, º F
Data Industrial® 340 BN/MB BTU Energy Transmitter
Page 22 July 2012