Energy Transmitter Owner's manual
Modbus Register Map
Model 340BN/MB Register Map
Register Name Address Data Type Read/Write
Temperature 1 40001 + 40002 IEEE 754 Float Read Only
Temperature 2 40003 + 40004 IEEE 754 Float Read Only
Flow Input (Hz) 40005 + 40006 IEEE 754 Float Read Only
Total Flow 40007 + 40008 IEEE 754 Float Read Only
Total Energy 40009 + 40010 IEEE 754 Float Read Only
Flow Rate 40011 + 40012 IEEE 754 Float Read Only
Energy Rate 40013 + 40014 IEEE 754 Float Read Only
K Factor 40015 + 40016 IEEE 754 Float Read Only
Offset 40017 + 40018 IEEE 754 Float Read Only
Temp Calc Mode 40019 + 40020 IEEE 754 Float Read Only
Flow Filter Coef 40021 + 40022 IEEE 754 Float Read Only
Temp Filter Coef 40023 + 40024 IEEE 754 Float Read Only
Specific Heat 40025 + 40026 IEEE 754 Float Read Only
Fluid Density 40027 + 40028 IEEE 754 Float Read Only
T1 A Coefficient 40029 + 40030 IEEE 754 Float Read Only
T1 B Coefficient 40031 + 40032 IEEE 754 Float Read Only
T1 C Coefficient 40033 + 40034 IEEE 754 Float Read Only
Temp 1 Offset 40035 + 40036 IEEE 754 Float Read Only
T1 A Coefficient 40037 + 40038 IEEE 754 Float Read Only
T1 B Coefficient 40039+ 40040 IEEE 754 Float Read Only
T1 C Coefficient 40041 + 40042 IEEE 754 Float Read Only
Temp 1 Offset 40043 + 40044 IEEE 754 Float Read Only
Installation & Operation Manual
Page 21 July 2012