Series 3000 Flow Monitor
RELAY OUTPUT CONFIGURATION
relay [1-5] func = [0-9] – relay function; relay 5 is the
pulse output
0: Totalizer
1: Alarm
2: Manual Control
relay [1-5] input = [0-8] – relay input; depends on source
for totalizer:
0: Flow 1 Total
for alarms:
0: Flow 1 Rate
relay [1-5] units = [0-19] – units on setpoints/rates;
depends on
src/input
ow units: same as 'ow [1-2] rate units' above
volume units: same as 'ow [1-2] total units'
relay [1-5] manual = [on/o] – manually set relay on or
o, if in manual mode
relay [1-5] rate = [x] – totalizer rate
relay [1-5] ctime = [0-10000] – pulse width in millisec-
onds
relay [1-4] latch = [on/o] – turn on/o relay latching
relay [1-4] setpoint = [x]
relay [1-4] releasepoint = [x]
ANALOG OUTPUT CONFIGURATION
analogout [1-2] func = [0-3]
0: Flow rate
3: PID control
analogout [1-2] src = [0-4]
for ow rate:
0: Flow 1 rate
for PID control:
0: Flow 1 rate
analogout [1-2] range = [0-1]
0: 0-20mA
1: 4-20mA
analogout [1-2] low = [x] – value corresponding to
0 (or 4) mA
analogout [1-2] high = [x] – value corresponding to
20mA
analogout [1-2] setpoint = [x] – PID setpoint
analogout [1-2] P = [x] – PID constants
analogout [1-2] I = [x] – PID constants
analogout [1-2] D = [x] – PID constants
RS485 COMM PORT CONFIGURATION
comm baudrate = [0-7]
0: Auto
1: 300
2: 1200
3: 2400
4: 9600
5: 19200
6: 38400
7: 76800
comm mstpaddr = [0-127] – BACnet/MSTP address
comm maxmaster = [0-127] – BACnet/MSTP max master address
comm devinst = [x] – BACnet device instance ID
comm mbslaveaddr = [0-255] – Modbus slave address
TROUBLESHOOTING
Trouble Codes:
1 Relay 1 totalizer rate exceeded
2 Relay 2 rate exceeded
3 Relay 3 rate exceeded
4 Relay 4 rate exceeded
5 Pulse out rate exceeded
20 Error reading EEPROM on faceplate
21 Error writing EEPROM
22 Analog Input card missing
24 Temperature Input card missing
25 Invalid ow units congured
26 Invalid volume units congured
27 Bad input frequency
29 Internal error calculating ow rate
31 Error reading from analog input AD converter channel 1
32 Error reading from analog input AD converter channel 2
36 Error writing to analog input AD converter channel 1
37 Error writing to analog input AD converter channel 2
50 Error reading I2C address 0 (relays, buttons, and LEDs)
51 Error writing to I2C address 0
52 Error reading I2C address 1 (analog input card control lines)
53 Error writing I2C address 1
54 Error reading I2C address 2 (temperature input card control lines)
55 Error writing I2C address 2
71 Watchdog timer reset occurred
82 Fatal error initializing EEPROM