Specifications

Fan Coil Thermostat Controller
Specification and Installation Instructions
www.neptronic.com Page | 7
20. max vdc analog output cooling
Default:
Range:
Increment:
10.0 Volt
0.0 to 10.0 Volt
0.1 Volt
Select the desired maximum voltage (span value) for cooling ramp. The maximum value (Step 20) is restricted by the minimum
value (Step 19). In other words, the maximum value should be greater than the minimum value.
21. set local reheat signal
Default:
Range:
OFF (no signal selected)
OFF, AnLG, AnLG, On/Of, On/Of, PuLS, PuLS
Select the desired signal output for reheat.
If you select AnLG (Analog, heating and fan), AO3 will be set to reheat.
If you select On/Of (On/Off heating and fan) or PuLS (Pulse heating and fan), TO3 will be set to reheat.
If you selected On/Of (On/Off heating and fan), or or PuLS (Pulse heating and fan), go to Step 24.
If you selected OFF, go to Step 26.
OFF (no signal
selected)
On/Of (On/Off
heating only)
PuLS (Pulse
heating only)
AnLG (Analog,
heating only)
On/Of (On/Off
heating and fan)
PuLS ( Pulse
heating and fan )
AnLG (Analog,
heating and fan)
22. min vdc analog output reheat
Default:
Range:
Increment:
0.0 Volt
0.0 to 10.0 Volt
0.1 Volt
Select the desired minimum voltage (zero value) of reheat ramp. The minimum value (Step 22) is restricted by the maximum
value (Step 23). In other words, the minimum value must be less than the maximum value.
23. max vdc analog output reheat
Default:
Range:
Increment:
0.0 Volt
0.0 to 10.0 Volt
0.1 Volt
Select the desired maximum voltage (span value) of reheat ramp. The maximum value (Step 23) is restricted by the minimum
value (Step 22). In other words, the maximum value must be greater than the minimum value.
Control Ramps
24. control ramp reheat
Default:
Range:
Increment:
2.0ºC [4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC [1ºF]
Select the desired value for the reheat proportional band. The heating symbol is also displayed.
25. control dead band reheat
Default:
Range:
Increment:
0.3ºC [0.6ºF]
0 to 5.0ºC [0 to 10.0ºF]
0.1ºC [0.2ºF]
Select the desired value for the reheat dead band. The heating symbol is also displayed.
26. control ramp HEATing
Default:
Range:
Increment:
2.0ºC [4ºF]
0.5 to 5.0ºC [1 to 10ºF]
0.5ºC [1ºF]
Select the desired value for the heating proportional band. The heating symbol is also displayed.