Specifications

NEW!
NETWORK & WIRELESS
808
NEW!
NETWORK & WIRELESS
13
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
BAPI WIRELESS SYSTEM OUTPUT MODULES
BA/COM, BA/ROM, BA/RYOM, BA/RYOL, BA/SOM, BA/VOM
Supply Voltage
COM Externally (loop) powered 9-36 VDC,
20 mA
ROM, VOM 9-30 VDC at 3 mA, or 17 to 30 VAC
at 0.1 VA
RYOM/RYOL 9-30 VDC at 15 mA, or 17 to 30 VAC
at 0.5 VA
SOM See SOM data sheet located under
"Related Documents" at
www.Kele.com
Analog Output
COM 4-20 mA, 9-36 VDC, loop powered
Impedance 750 at 24 VDC
ROM-102 10 k type 2 thermistor curve, 5 VDC
excitation maximum
ROM-103 10 k type 3 thermistor curve, 5 VDC
excitation maximum
SOM-10 0 to 10 VDC, 10 k maximum
SOM-60 0 to 10 k, linear
SOM-80 0 to 20 k, linear
SOM-84 10 to 30 k, linear
SOM-102 10 k Type 2 thermistor 50° to 90°F
(10° to 32°C)
VOM-10 0-10 VDC, 10 k maximum
Digital Outputs Solid state dual FETs, NO or NC 40
VAC/VDC, 150 mA maximum 1μA
leakage in off state 15 on-state
resistance
Connections Terminal strip (inter-lockable)
Update Interval 10 seconds
Operating Temperature 32° to 140°F (0° to 60°C)
Operating Humidity 5-95% RH non-condensing
Materials Of Construction
ABS Plastic, UL94V-0
Dimensions 2.75"H x 2.34"W x 1.2"D
(7.0 x 5.9 x 3.0 cm)
Weight 0.3 lb (0.14 kg)
RoHS Statement Ye s
Warranty 1 year
DESCRIPTION
The BAPI BA/ROM, VOM, COM, and RYOM Wireless
System Output Modules are specifically designed to
connect to any BA/RCV receiver and communicate over an
RS485 communication trunk to generate standard output
signals for any BAS system. A total of 127 modules may be
interspersed on the RS485 trunk. Each will output a signal
representative of its assigned wireless transmitter located
remotely. Each module may be powered from the receiver
power bus, or individually, based on overall system power
requirements.
The BAPI BA/ROM Thermistor Simulation Output Module
converts a wireless transmitter temperature signal according
to a standard thermistor curve. The two standard curves
are 10 K Type 3 and a 10 K Type 2, with a resistance
temperature response of 35° to 120°F (1° to 50°C).
The BAPI BA/VOM Voltage Output Module converts a
wireless transmitter temperature signal to a standard voltage
signal. The two standard voltage outputs are 0-5 VDC and
0-10 VDC, with voltage temperature responses based on
individual models.
The BAPI BA/COM Current Output Module converts
a wireless transmitter temperature signal to a standard
4-20 mA current signal. The 4-20 mA current is typical of a
loop powered (9-36 VDC) device with current temperature
responses based on individual models.
The BAPI BA/RYOM Digital Output Module converts the
pushbutton on a wireless room temperature transmitter to
a solid-state relay closure for AC or DC voltages (5 second
momentary actuation). NO or NC solid-state contacts are
available, based on individual models.
The BAPI BA/RYOL Digital Output Module converts the BA/
WDI digital input tranmitter signal to a latching relay output.
NO or NC contacts are available, based on individual models.
The BAPI BA/SOM Setpoint Output Module converts the
setpoint data from a wireless receiver to a resistance or
voltage output.
FEATURES
Provide BAS point wiring
127 modules per system include:
Thermistor simulation for temperature
0-10 VDC or 0-5 VDC signals
4-20 mA signals
Solid-state contacts
FCC license pre-approved
Built-in error detection
Built-in fail-safe positions
Snap-track mounting
SPECIFICATIONS
BA/SOM-16-EZ, BA/VOM-05-C-EZ,
BA/ROM-102-EZ
March 2014