Specifications
NEW!
NETWORK & WIRELESS
796
NEW!
NETWORK & WIRELESS
13
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
WIRING
Battery Two AA 3.6V lithium batteries
(included)
Frequency 418 MHz
Transmission Power 1 mW
Range 100 ft
Update Interval 10-17 seconds (fixed)
Analog Input
BA/WAI-05 0-5VDC, Impedance > 30KΩ
BA/WAI-10 0-10VDC, Impedance > 50KΩ
BA/WAI-420 4-20 mA, Impedance = 100Ω
BA/WTS Any 10K Type 2 Thermistor, range
-40 to 185°F (-40 to 85°C)
Digital Inputs
BA/WDI Dry contact, > 20 seconds
(< 10Ω closed, >250Ω open)
Operating Temperature 32° to 140°F (0° to 60°C)
Operating Humidity 5 to 95% RH, (non-condensing)
Enclosure NEMA 4 (IP66)
Dimensions 5.0"H x 4.1"W x 2.5"D
(12.7 x 10.4 x 5.4 cm)
Weight 0.5 lb (0.22 kg)
Approvals FCC ID# T4F16963N16964
(418 MHz only)
RoHS Statement Ye s
Warranty 2 year
BAPI WIRELESS UNIVERSAL TRANSMITTERS
BA/WAI SERIES, BA/WDI, BA/WTS
DESCRIPTION
The BA/W Series Wireless Universal Input Transmitters are
designed to monitor 0-5VDC, 0-10VDC or 4-20 mA signals
and transmit that analog value to a receiver. The Digital
Input version monitors any dry contact status input and
transmits
that On/Off status to the receiver. The Thermistor
Temperature Input version takes any 10K Type 2 thermistor
sensor and transmits it to any BAPI receiver. All models
transmit their data every 10-17 seconds. The units are battery
operated and only require wiring from the remote input
sensor.
FEATURES
• Two Year Battery Powered with Replaceable Battery
• 0-5, 0-10 and 4-20mA Analog Input Models
• Digital Input (dry contact) Model
• Thermistor Temperature Input Model
• 100' open air range, 1,000' range with a Repeater
• Transmission Interval from 10-17 seconds
• Easy Two-Wire Termination and Easy Setup Mode
WIRING - FIGURES ARE ON NEXT PAGE
SPECIFICATIONS
BA/EZ RCV 418
Receiver
418 MHz
BA/EZ ROM
Output
1
BA/EZ COM
Output
127
BA/TEMP
Transmitter
BA/EZ RCV 900
Receiver
900 MHz
BA/EZ ROM
Output
1
BA/EZ COM
Output
127
BA/EZ RPT
Repeater
418 MHz
BA/TEMP
Transmitter
Battery Installation:
Battery supplied: Two-3.6 VDC Lithium batteries
(Figure 1) Install both batteries per the +/- indication on the battery holder board.
Note: Both batteries face the same way. (Unit will run on one battery if needed)
Input Sensor Wiring Description:
Voltage: Wire the + signal to the + terminal on the battery board.
(Figure 2) Wire the – signal to the – terminal on the battery board.
Current (sync): Wire the 4-20 mA current signal (-) from the sensor to + terminal on the battery board.
(Figure 3) Wire the – of the power supply feeding the sensor to the sensor to the – terminal on the battery board.
Wire the + of the power supply feeding the sensor to the + of the sensor.
Current (source): Wire the + signal to the + terminal on the battery board.
(Figure 4) Wire the – signal to the – terminal on the battery board.
Provide + power to sensor
Provide – power to sensor
Thermistor Sensor: Wire either lead to the + terminal of the battery board. (Non-Polar)
(Figure 5) Wire the other lead to the – terminal of the battery board. (Non-Polar)
Contact Input: Wire either lead to the + terminal of the battery board. (Non-Polar)
(Figure 6) Wire the other lead to the – terminal of the battery board. (Non-Polar)
* The transmission range from repeater to receiver is 1000 feet.
March 2014