Specifications
NEW!
NETWORK & WIRELESS
718
NEW!
NETWORK & WIRELESS
13
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
ORDERING INFORMATION
BACNET AND UNIVERSAL GATEWAYS
LGATE-9XX SERIES
MODEL DESCRIPTION
LGATE-900 Lonworks to BACNET LGATE Gateway
LGATE-950 Universal LGATE Gateway with one ext. port
LGATE-951 Universal LGATE Gateway with two ext. ports
10/100Base-T
(RJ45)
-
12-35 VDC
12-24 VAC
+
MS/TP
Port
Termination
(L-Term)
CEA-709
123456 8151617
POWEREthernetRS-485
Serial Terminal
RESET
ACT
LINK
ACT
ACT
BACnet/IP
Ethernet
BACnet/IP
POWER
STATUS
Connectors
MS/TP 1 Input GND
2 Input + (B) non-inverting input
3 Input
-
(A) inverting input
CEA-709 4 Input EARTH GND
5 Input B
6 Input A
Ethernet 8 10/100Base-T (RJ45)
POWER 15 Power supply input EARTH GND
16 Power supply input MINUS
17 Power supply input PLUS
Do NOT connect to
EARTH GND
SERIAL 40 EIA-232 (DB9 male)
Buttons
RESET Reset
STATUS Send “I AM” message
Status LEDs
A Green flashing fast Traffic on MS/TP port
B Green flashing fast Traffic on CEA-709 port
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port
C Green IP port is fully functional
Yellow IP port functional but
config. is not up-to-date
Red IP port is non-functional
Flashing at 1 Hz IP port is not commissioned
OFF IP port is not active
D Green Ethernet link
E Green flashing Ethernet traffic
F Green BACnet IP enabled
G Green Power
H OFF Normal operation
NOTE: If terminal 1 is not connected make a
short between terminal 15 and 16,
and connect to EARTH GND.
40
A
B
C
F
E
D
G
H
FT
2 x USB-A
USB1
USB2
USB-B
2 x 10/100Base-T
(RJ45)
Ethernet1
Ethernet2
BA
M-Bus, KNX TP1,
ZigBee PRO
GND
131415
EXT2
BA
GND
1011 12
EXT1
789
456
BA
FT
TP/FT-10
-
+
GND
RS-485
Modbus RTU,
BACnet MS/TP
-
24-35 VDC
24 VAC
+
123
POWER
microSD
Connectors
POWER 1 Power supply input EARTH GND
2 Power supply input MINUS
Can be connected to EARTH GND
3 Power supply input PLUS
Do NOT connect to
EARTH GND
Modbus 4 Input GND
BACnet 5 Input +
MS/TP 6 Input
-
TP/FT-10 7 Input EARTH GND
8 Input B
9 Input A
EXT1 10 Input GND
M-Bus, 11 Input B
KNX TP1 12 Input A
ZigBee
EXT2 13 Input GND
M-Bus 14 Input B
KNX TP1 15 Input A
ZigBee
Connectors
USB1 USB-A USB Host
USB2 USB-A USB Host
USB-B USB-B PC
Ethernet1 RJ45 10/100Base-T
Ethernet2 RJ45 10/100Base-T
microSD slot microSD card
max. 2 GB
Buttons
RESET Reset
DIAL Turn-and-Push Dial
0.2 - 2.5 mm
2
7
Weidmüller
BLZP 5.08/03/180
RESET
DIAL
DISPLAY
LGATE 900 LGATE 95x
WIRING