Specifications
NEW!
785
NETWORK & WIRELESS
NETWORK & WIRELESS
13
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
FRONTIER 2.0 WIRELESS REMOTE TEMPERATURE SYSTEM
SST2630
INSTALLATION
ORDERING INFORMATION
SST2630 Wireless Remote/Strap-on Temperature Sensor
Temperature ranges
A 25° to 125°F
B 0° to 200°F
C - 40° to 160°F
Enclosure
E NEMA4 enclosure (Optional)
Example: SST2630AE Sensors in NEMA4 enclosure with
25°F to 125°F range.
SST2630 A
-
-
E
Wireless SST2630 sensors should be installed within 200 to 500 feet of the receiver. RR2552 signal repeaters can be installed as
needed to increase transmission distance between sensors and receivers.
To select the proper sensor location, first install and power the receiver. Observing polarity, insert the battery into the sensor to
activate it. The mesh networked Frontier 2.0 system does not require any additional wireless equipment to determine the proper
location of the sensors.
While the sensor is attempting to connect to the receiver, the Data-Link LED will blink rapidly 8-10 times every 10 seconds.
Once a connection has been established, the Data-Link LED will blink once to indicate the data transmission has been received
successfully. The Data-Link LED will continue to blink once for every data transmission. The data transmission rate is programmed
into the sensor (normally 1 minute intervals). To manually initiate a data transmission press the push button switch located by the
negative terminal of the battery.
The sensor probe should be mounted under any insulation in direct contact with the pipe using metal pipe straps. For proper
measurement of temperature, thermal conductive compound should be used in between the sensor probe and the pipe. The
installation should be wrapped with insulation to reduce the effect of ambient air.
The plastic housing of the sensor can either be mounted on the pipe with metal pipe strap or wall mounted.
Locate and record the sensor TXID numbers located on a label on the inside of the enclosure cover. This information will be
needed later to set up the receiver.
The sensor has a Low Battery LED that will start to blink continuously when the battery voltage is low. A low battery signal is also
sent to the receiver for remote indication that the battery should be replaced. If the battery is not replaced in approximately 2
months the battery voltage will become so low that the Low Battery and Data-Link LEDs will not blink. Replace the battery and the
Data-Link LED will start blinking while the sensor is re-establishing communications with the receiver.
Then attach the cover of the sensor by installing the four screws.
CAUTION:
Sensors, repeaters and receivers should NOT be installed in the following areas:
- Inside metal enclosure or panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or a large body of water
Transmission distance and performance will be drastically reduced.
CAUTION:
Do not use this product in any safety related applications where human life may be affected.