Specifications
NEW!
783
NETWORK & WIRELESS
NETWORK & WIRELESS
13
WE MAKE IT EASY.
kele.com 888-397-5353 USA
Wireless digital transmitters should be installed within 200 to 500 feet of the receiver. RR2552 signal repeaters can be installed
as needed to increase transmission distance between sensors and receivers.
Sensor Location:
To select the proper sensor location, first install and power the receiver. Observing polarity, insert the battery into the sensor
to activate it (for battery operation, move the voltage selection jumper to battery mode before inserting the battery). The mesh
networked Frontier 2.0 system does not require any additional wireless equipment to determine the proper location of the
sensors.
While the sensor is attempting to connect to the receiver, the Data-Link LED will blink rapidly 8-10 times every 10 seconds.
Once a connection has been established the Data-Link LED will blink once to indicate the data transmission has been
received successfully. The Data-Link LED will continue to blink once for every data transmission. The data transmission rate is
programmed into the sensor (normally 1 minute intervals). To manually initiate a data transmission, press the push button switch
located by the negative terminal of the battery. Once the location has been determined, mount the RT2630 remote transmitter on
a wall using four #8 screws.
Determine if the RT2630 transmitter will be powered by 24 VAC/VDC or by batteries on a permanent basis.
For 24 V Operation:
If the device is to be powered by 24 V (AC or DC), connect 24 V to the input terminals using 18-20 AWG wire.
For Battery Operation:
If the device is to be powered using the optional DL123A batteries (included) – remove the voltage selection jumper and
reposition it for battery operation.
NOTE:
The device is shipped with the voltage selection jumper installed in the 24 V position. For proper operation it is
important to use the correct type of battery. Lithium 3.0V 1400 mAh (Duracell DL123A) batteries. Installing the battery or
applying 24 VAC will activate the transmitter.
Sensor Inputs:
Wire the sensor inputs to the appropriate terminals using 18 AWG wire. Record the sensor location on the wiring label located
inside the cover. Attach the cover using the four screws.
FRONTIER 2.0 WIRELESS UNIVERSAL INPUT TRANSMITTER MODULE
RT2630 SERIES
INSTALLATION
ORDERING INFORMATION
CAUTION: Sensors, repeaters and receivers should NOT be installed in the following areas:
- Inside metal enclosure or panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or a large body of water
Transmission distance and performance will be drastically reduced.
CAUTION:
Do not use this product in any safety related applications where human life may be affected.
CAUTION:
Observe polarity when connecting analog outputs to controller inputs
RT2630 Input Module with 4 Digital Inputs and 4 Analog Inputs
A 4 Resistance inputs (20KΩ)
B 4 Voltage inputs (0-10VDC)
C 4 Current inputs (0-20 mA)
Power options
DC 24VDC or battery
AC 24VAC or battery
Example: RT2630-A-AC Input module with 4 digital inputs
and 4 resistance inputs (20KΩ), 24VAC or battery.
RT2630
A
-
-
AC
March 2014