Determining Repeater Location:
To select the proper repeater location, first install and power the receiver or transceiver. The receiver will have a Network ID
assigned to it during initial programming. The repeater must have the same Network ID as the receiver or transceiver. Set the
Network ID on the repeater using the Network ID DIP Switch.
The battery operated Test Mode is intended to be used only during the initial installation to determine the optimum location for a
repeater in the system prior to wiring 24 VAC to the repeater. To operate the unit in Test Mode, move the jumper (J1 located near
the battery terminals on the PWB) from 24 VAC to Battery. Install (2) batteries - Type 3.0V LiMNO2 1400 mAH (Duracell DL123A).
The repeater is now functional and can be moved to different locations to determine optimal system performance.
While the repeater is attempting to connect to the receiver, the Data LED will blink rapidly. Once a connection has been
established, the Data-Link LED will blink once to indicate the data transmission has been received and transmitted successfully.
The Active LED will blink once every second to indicate that the repeater is functional.
A signal repeater can be installed 200 to 500 feet from a receiver as needed to improve transmission distance/reliability between
sensors and the receiver.
Performance of the device is generally better when the repeater is installed elevated from the ground as much as possible.
Mount the RR2552 to the wall using four #10 screws.
Check to see that the Test Mode Jumper (J1) has been moved from " Battery" to "24 VAC."
Connect 24 V 60 Hz to the power input terminals using 16-20 AWG wire.
FRONTIER 2.0 SPREAD SPECTRUM REPEATER
RR2552
INSTALLATION
ORDERING INFORMATION
MODEL DESCRIPTION
RR2552B Two way repeater
RR2552BE Two way reapeater in NEMA4 enclosure
CAUTION:
Sensors, Repeaters and receivers should NOT be installed in the following areas:
- Inside metal enclosure or panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or a large body of water
Transmission distance and performance will be drastically reduced.
CAUTION:
Do not use this product in any safety related applications where human life may be affected.
CAUTION:
For long term operation the repeater requires 24 VAC. The repeater will function for only 4 to 6 hours in "Test
Mode" on a set of batteries. Observe polarity when connecting analog outputs to the controller inputs.