Specifications
NEW!
777
NETWORK & WIRELESS
NETWORK & WIRELESS
13
WE MAKE IT EASY.
kele.com 888-397-5353 USA
Configuration
The RM2432 Receiver can be configured to accept inputs from up to 8 wireless sensors. Refer to the RM2432D Configuration
Manual for instruction.
Installation
Mount the RM2402/RM2432 Receiver as close to the controller as possible using four #8 screws.
Select 0-10VDC or 0-5VDC output by moving the J4 jumper (RM2432 only).
Using the RM2402/RM2432 configuration information, connect the analog and digital outputs to the appropriate control input
terminals on the controller using 20 AWG wire. The controller input connecting to the RM2432 should have a minimum analog
input resistance of 20K Ω.
Note: Always connect the Low Battery (or Lost Sensor) relay contact output to the appropriate alarm input on the
controller. (RM2432D)
Connect 24 VAC 60 Hz or 24 VDC to the input terminals using 20 AWG wire. Check all connections before applying power to the
unit.
Wireless Sensor Status Indications
The status of the sensors assigned to the outputs of the RM2402/RM2432D are displayed by 8 for (RM2432) 2 for (RM2402)
LEDs on the top of the plug-in status module board as shown:
- Sensor Out (Lost) = Off
- Sensor In (Normal) = On
- Battery Low (Alarm) = Blink
FRONTIER 2.0 WIRELESS ANALOG AND DIGITAL RECEIVERS
RM2402D AND RM2432D
INSTALLATION
ORDERING INFORMATION
MODEL DESCRIPTION
RM2402D Output receiver with two (2) digital outputs (relay contacts)
RM2402D-24DC Same as RM2402D except 24 VDC power
RM2402DE Same as RM2402D except in NEMA4 enclosure
RM2402DE-24DC Same as RM2402DE except 24 VDC power
RM2432D Output receiver with four (4) analog output (0-10 VDC or 0-5 VDC selectable)
and four (4) digital outputs (relay contacts)
RM2432D-24DC Same as RM2432D except 24 VDC power
RM2432DE Same as RM2432D except in NEMA4 enclosure
RM2432DE-24DC Same as RM2432DE except 24 VDC power
CK2432-K Programming Set-Up Cable
CAUTION:
Sensors, Repeaters and receivers should NOT be installed in the following areas:
- Inside metal enclosure or panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or a large body of water
Transmission distance and performance will be drastically reduced.
CAUTION:
Do not use this product in any safety related applications where human life may be affected.
CAUTION:
Observe polarity when connecting analog outputs to the controller inputs.