Specifications
NEW!
715
NETWORK & WIRELESS
NETWORK & WIRELESS
13
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
RLE TECHNOLOGIES PROTOCOL COVERTER
RAPTOR PROTOCOL CONVERTER
DESCRIPTION
The Raptor Protocol Converter connects directly to equipment
and converts the SNMP, BACnet, and Modbus protocols to
one or more of these same protocols for integration into a
building management system (BMS) or network management
system (NMS). The Protocol Converter is ideal for situations
where data from monitored equipment is incompatible with
the protocols used by the BMS or NMS, such as in cases
where legacy monitoring systems are present. The ability of
the Protocol Converter to accept up to 1,024 inputs over 32
modules means flexible integration with multiple alarm and
management systems with the use of one simple device. In
addition, the Dual Port Protocol Converter provides a cost-
effective means to connect to multiple trunk lines with two
additional Modbus EIA-485 ports.
FEATURES
• Multiple input and output protocols
• Monitor up to 1,024 Modbus registers, OIDs, or instances
• Connect up to 32 units/modules/nodes
• Connect to multiple trunk lines with Dual Port Protocol Converter
• Alarm notification through email, SNMP
• Web configuration
Supply Voltage 24 VAC/VDC @ 600mA max,
50/60 Hz
Communication Ports
Ethernet 10/100BaseT, RJ45 connector;
500VAC RMS isolation
EIA-232 DB9 female connector; 9600 baud;
No parity, 8 data bits, 1 stop bit
EIA-485 1200, 2400, 9600 or 19200 baud
(selectable); Parity: none, even or
odd, 8 data bits, 1 stop bit
Protocol
TCP/IP; HTML, TFTP
SNMP V1: V2C MIB-2 compliant; NMS
Manageable with Get
Modbus (EIA-485) Modbus Master/Slave; RTU mode;
Supports Master codes 01, 02, 03,
04; Slave code 03
Modbus TCP/IP Modbus Master/Slave; TCP/IP
transmission protocol
BACNet/IP ASHRAE STD 135-2004 Annex
J; Port 3 on Dual Port Protocol
Converter is BACnet MS/TP capable
(Slave only)
SMTP (email) Supports Client Authentication (plain
and login); compatible with ESMTP
Servers
Terminal Emulation (EIA-232)
VT100 compatible (for configuration
and diagnostics only)
Indicator
Network 1 Green/Red LED: Link/No Link; 1
Green Active (additional LEDs for
Dual Port Protocol Converter)
EIA-485 Status 2 Green Transmit and Receive
LEDs (additional LEDs for Dual Port
Protocol Converter)
Security Login
Web Browser Access (Ethernet)
1 Web password Read Only; 1 Web
password Read/Write
Terminal Emulation Access
None
Protocols In SNMP, Modbus EIA-485, Modbus
TCP/IP, BACnet/IP
Protocols Out SNMP, Modbus EIA-485, Modbus
TCP/IP, BACnet/IP; BACnet MS/
TP (Port 3 of Dual Port Protocol
Converter only)
Maximum Number of
units/modules/nodes 32
Maximum Number of
registers/OIDSs/instances
1024
Operating Temperature 32° to 122°F (0° to 50°C)
Storage Temperature -4°to 185°F (-20° to 85°C)
Operating Humidity 5-95% RH non-condensing
Mounting Desktop or rack mount (brackets
included)
Dimensions 9.8"W x 5.3"D x 1.8"H
(248 x 135 x 46 mm)
Weight 2.32 lb. (1.05kg)
Approvals CE; ETL listed: conforms to UL
61010-1, EN 61010-1; certified to
CSA C22.2 NO. 61010-1; RoHS
compliant
SPECIFICATIONS