Specifications
NEW!
NETWORK & WIRELESS
756
NEW!
NETWORK & WIRELESS
13
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
55°
10 m
32.8 ft
10 m
32.8 ft
X
0°
Top View
Side View
10 m
32.8 ft
10 m
32.8 ft
0°
46.5°
Y
SPECIFICATIONS
FLEXIBLE BACNET THERMOSTAT
FLEXSTAT
DESCRIPTION
The FlexStat Series of intelligent thermostats can monitor
temperature/humidity/motion-sensing, and are wall-
mounted. In addition the FlexStat comes with BACnet MS/TP
communications standard. The FlexStat simplifies networked
zone control for common HVAC equipment. Example
applications are packaged rooftop units, air handlers, fan
coil units, and heat pumps. The on-board library of programs
permits rapid configuration of a wide range of HVAC control
applications via the FlexStat’s display and buttons.
FEATURES
• User-friendly English-language menus on a 64 x 128
pixel, dot-matrix LCD display with 5 buttons for data
selection and entry
• Built-in, factory-tested libraries of configurable
application control sequences
• Schedules can easily be set by weekdays (Mon. -
Fri.), weekend (Sat. - Sun.), entire week (Mon. -Sun.),
individual days, and/or holidays
• Six On/Off and independent heating and cooling set
point periods are available per day
• Three levels of password-protected access (user/
operator/administrator)
MOTION / OCCUPANCY SENSOR (OPTIONAL) PATTERN
BACnet 120000 Series
• Integral temperature and optional humidity and/or
motion sensors
• Multiple models available
• 72-hour power (capacitor) backup and a real time clock
for network time synchronization or full stand alone
operation
Supply Voltage 24VAC 50/60 Hz
Supply Current 13 VA
Display 64 x 128 pixel dot matrix LCD
Analog Input 0-12 VDC (Active/Passive)
10K thermistor (type 2 or 3)
Analog Output 0-12 VDC, 20 mA (maximum)
Digital Output 1 A maximum each or total of
1.5 A per bank of relays
Sensor Type
Humidity (optional) CMOS
Temperature (with humidity)
CMOS
Temperature (without humidity)
10K Type 2
Motion (optional) Passive infrared with 33 feet
(10 meter) range
Accuracy
Humidity (optional) ±2% RH (10 to 90% RH)
Temperature (with humidity)
±0.9°F (±0.5°C)
Temperature (without humidity)
±0.36°F (±0.2°C)
Range
Humidity (optional) 0 to 100% RH
Temperature (with humidity)
36° to 120°F (2.2 to 48.8°C)
Temperature (without humidity)
48° to 96°F (8.8 to 35.5°C)
Response Time Humidity (optional)
< 4 seconds
Operating Temperature 34° to 125°F (1.1 to 51.6°C)
Operating Humidity 0 to 90% RH (non-condensing)
Dimensions 4.1"H x 5.5"W x 1.1"D
(10.6 x 14.1 x 1.1 cm)
Weight 0.48 lb (0.22 kg)
Approvals cULus Listed File #E145832, FCC
Warranty 5 years
March 2014