KELE CONSTANT VOLUME ZONING SYSTEM
KTEC ZONING SYSTEM
Supply Voltage 19 to 30 VAC, 50/60 Hz
Supply Current 2 VA @ 24 VAC
Analog Input
KTEC2647Z Resistive inputs (RS and UI3) for
10KΩ Type II thermistor
KTEC2664Z Resistive inputs (RS, OS, and DS) for
10KΩ Type II thermistor
Analog Output 0 to 10 VDC into 2kΩ resistance load
(minimum)
Digital Inputs
KTEC2647Z Dry contacts across terminal scom to
terminals BI1 and BI2
KTEC2664Z Dry contact across terminal scom to
terminal BI1
Auxiliary Contacts Triac output 19 to 30 VAC, 15 mA
to 1 A continuous current, 3A peak
in-rush current
Static Pressure 0 to 5 VDC for full static pressure
range selected
Accuracy ±0.9°F (±0.5°C) at 70°F (21°C)
Sensor Type 10k ohm NTC thermistor (Local)
Setpoint Range Heating 40° to 90°F (4.5° to 32°C)
Cooling 54° to 100°F (12° to 37.5°C)
Deadband 2°F (1°C)
Number of Zones 31 zones maximum per 1 rooftop
controller
Operating Temperature 32° to 122°F (0° to 50°C)
Display -40° to 122°F (-40° to 50°C) in 0.5°
increments
Operating Humidity 0 to 95% RH (non-condensing)
Dimensions 4.9"H x 3.4"W x 1.1"D
(12.5 x 8.6 x 2.9 cm)
Weight 0.75 lb (0.34 kg)
Approvals
United States UL Listed, CCN XAPX, Under
UL 873, Temperature Indicating
and Regulating Equipment FCC
Compliant to CFR 47, Part 15,
Subpart B, Class A, RoHS
Canada UL Listed, CCN XAPX7, Under CAN/
CSA C22.2 No. 24
RoHS Statement Ye s
Warranty 3 years
DESCRIPTION
The technologically advanced KTEC Zoning Control
System provides efficient space temperature control for
constant volume zoning systems in multi-zone heating and
cooling applications. This cost-effective zoning control system
can operate as a stand-alone system, or it can be mapped
into a supervisory controller via a BACnet - Master-Slave/
Token-Passing (MS/TP) Bus to enable remote monitoring and
programmability within a Building Automation System (BAS).
FEATURES
• Fully scalable zoning control system meets the
requirements of small and large zoning control
systems
• BACnet MS/TP communication provides compatibility
with a proven communication network
• True stand-alone zoning control system offers
additional application flexibility
• Backlit Display offers real-time control status of
the environment in easy-to-read, English plain text
messages with constant backlight that brightens
during user interaction
• Simplified setpoint adjustment enables the user to
change the setpoint by simply pressing the UP/DOWN
arrow keys
• Configurable binary inputs provide additional inputs
for advanced functions such as remote night setback,
service or filter alarms, motion detector, and window
status
• Over 20 configurable parameters enable the zoning
control system to adapt to applications with varying
requirements, allowing installer parameter access
without opening the controller cover
CONTROL LAYOUT
SPECIFICATIONS
KTEC2664Z Rooftop
Controller
KTEC2647Z Zone
Controller
70.0°F
Room Temp
YES NO
SCROLL
FAN
MENU
HEAT COOL
Backlit, plain text
LCD is easy to read
in any condition
Five keys on the zone controller
make operation easy and intuitive
LEDs indicate
system activity
KTEC2664Z Rooftop Controller
OVERRIDE
HEAT COOL
70.0°F
Room Temp
Backlit, plain text
LCD is easy to read
in any condition
Three keys on the zone controller
make operation easy and intuitive
LEDs indicate
system activity
KTEC2647Z Zone Controller
See installation instructions for wiring diagrams