Specifications
NEW!
751
NETWORK & WIRELESS
NETWORK & WIRELESS
13
WE MAKE IT EASY.
kele.com 888-397-5353 USA
VISONIC AUTO DIALER
DL-125C
Telephone line
failure alert
24 to 30 VAC
Alarm-2
RedRed
Grn
Alarm-1
No alarm
internal
connection
(opens on alarm)
Phone
Line
Hand
Set
To wall jack
To phone
Earth
12/24
VDC
11-28 VDC
Z1 Z2
L F
WIRING
PROGRAM MEMORY LOCATION CHART
ORDERING INFORMATION
MODEL DESCRIPTION
DL-125C Auto dialer for remote alarm voice indication
DL-125C
Memory Location Description (code option) Entry Limits Program Format Factory Default
1 1st phone number for Z1, (Alarm 1) 20 digits [PR] [1] [#] [NUM] [#] NONE
2 2nd phone number for Z1, (Alarm 1) 20 digits [PR] [2] [#] [NUM] [#] NONE
3 3rd phone number for Z1, (Alarm 1) 20 digits [PR] [3] [#] [NUM] [#] NONE
4 4th phone number for Z1, (Alarm 1) 20 digits [PR] [4] [#] [NUM] [#] NONE
5 1st phone number for Z2, (Alarm 2) 20 digits [PR] [1] [#] [NUM] [#] NONE
6 2nd phone number for Z2, (Alarm 2) 20 digits [PR] [2] [#] [NUM] [#] NONE
7 3rd phone number for Z2, (Alarm 2) 20 digits [PR] [3] [#] [NUM] [#] NONE
8 4th phone number for Z2, (Alarm 2) 20 digits [PR] [4] [#] [NUM] [#] NONE
9 Not used or accessible N/A N/A N/A
10 0 = enable, 1 = disable listen-in 0 or 1 [PR] [10] [#] [CODE] [#] 1
11 Dialing method, 0 = DTMF, 1= Pulse 0 or 1 [PR] [11] [#] [CODE] [#] 0
12 Alarm Z1 dialing attempts 1 - 15 [PR] [12] [#] [NUM] [#] 4
13 Alarm Z2 dialing attempts 1 - 15 [PR] [13] [#] [NUM] [#] 4
14 Alarm delay before callout, (seconds) 1 - 255 [PR] [14] [#] [SEC] [#] 3
15
Order of segment messages
0 = Alarm segment first
1 = Location segment first
0 or 1 [PR] [15] [#] [CODE] [#] 1
16 LF output logic 0 = NC, 1 = NO 0 or 1 [PR] [16] [#] [NUM] [#] 1
17-19 Not used or accessible N/A N/A N/A
20 Recorded message repeats 1 - 255 [PR] [20] [#] [NUM] [#] 4
21 Listen-in duration (seconds) 1 - 255 [PR] [21] [#] [SEC] [#] 60
22 Z1 input definition, 0 = NO, 1 = NC 0 or 1 [PR] [22] [#] [CODE] [#] 0
23 Z2 input definition, 0 = NO, 1 = NC 0 or 1 [PR] [23] [#] [CODE] [#] 0
24 Acknowledgement reset 0 or 1 [PR] [24] [#] [CODE] [#] 1
Backup = 1, All numbers are called regardless of acknowledgement. Non-backup = 0, after the first acknowledgement no other calls are made.
CAUTION: Additional comments and/or requirements
This device is not a life safety device and should not be used for life safety applications.
March 2014