VISONIC AUTO DIALER
DL-125C
Supply Voltage 11-28 VDC
Supply Current 20 mA standby, 105 mA maximum
Connection Terminal strip
Phone Tone (DTMF) or pulse
Impedance 600Ω
Alarm Input (AL) 2 alarm inputs
AL 1 Configurable NO or NC
AL 2 Configurable NO or NC
Alarm Out (LF) Phone line fail, 30 Volt triac
Dial Alert LED indication during use
Microphone Built-in
Controls 12-key number pad
1 program and 1 stop button
2 alarm buttons (AL-1, AL-2)
Memory EEPROM, non-volatile
No. of Calls 4 calls per alarm maximum or 2
pager calls maximum
Numbers / dial-out 20 numbers maximum
Messages 2, each using 2 segments
Message 1, segment 1 & 2
Message 2, segment 1 & 3
Segment 1 14.5 seconds, activated for both
alarms
Segment 2 2.5 seconds, identifies alarm AL-1
Segment 3 2.5 seconds, identifies alarm AL-1
Message Length
Overall 20 seconds for all segments
Dialing Attempts Adjustable, 1-15
Message Repeats Adjustable, 1-255
Time Between Repeats 3 seconds
Dialer trigger delay Adjustable, 1-255 seconds
Listen-in Function Adjustable (enable/disable)
Listen-in Duration Adjustable, 1-255 seconds
Acknowledge First call or all calls (enable/disable)
Enclosure NEMA 1
Operating Temperature 32° to 122°F (0° to 50°C)
Dimensions 4.25"H x 6.0"W x 1.4"D
(10.5 x 15.0 x 3.5 cm)
Weight 0.5 lb (0.24 kg)
Approvals CE
Warranty 1 year
DESCRIPTION
The DL-125C automatic programmable speech dialer is
designed for twin contact closure input. It will automatically
dial out and alert up to four numbers per alarm. The
20-second voice message is digitally stored in non-volatile
memory and may be changed at any time. The unit is
powered by 12 VDC and may be connected to any phone
line with pulse or tone dialing. The DL-125C is ideal for
panel mounting and alarming any contact input such as
temperature high or low limits, water leak detection, efrigerant
leak, CO2 limit alarm, control failure, and a host of other
purposes.
FEATURES
• Normally-open or normally-closed dual contact input
• Screw terminal strip connection
• 20 seconds of digitally stored voice
• Site monitor microphone
• Line seizure capability
• Compact design
• Keypad interface
• Phone line failure output
For a secure way of lif
e
SPECIFICATIONS
DL-125-C
OPERATION/APPLICATION
Upon alarm initiation, the DL-125C pauses for a
programmable time (1-255 sec), then hangs up any device
on the same phone line (line seizure) and dials out to the first
of four possible phone numbers. If someone answers, the
20-second message is delivered. The DL-125C will attempt to
dial each phone number between 1 and 15 times (decided at
set-up) before abandoning any further attempts. Once a call
is answered and the 20-second message is delivered, the unit
waits three seconds for an acknowledgment (touch tone digit
1). The recipient can cancel further call-outs, or the device
will continue to call the remainder of the phone numbers. If
acknowledged, a "listen in" feature is enabled so the called
party can audibly monitor the site for 10 seconds (this can
be programmed for a longer time). After the call cycle is
complete, the DL-125C moves on to the next phone number
or stops (as programmed) after first acknowledgment.
March 2014