PROVIDES CONNECTIVITY BETWEEN ETHERNET AND RS-485 BASED NETWORKS
ETH-1000
Supply Voltage 7 - 24 VDC
Supply Current 70 mA @ 24VDC
Communication Ethernet Communications
IEEE 802.3 10/100 Mbps data rate
10BASE-T, 100BASE-TX physical
layer 100 m (max) CAT5 cable
length
MS/TP Communications
ANSI/ASHRAE 135 (ISO 16484-5)
9600, 19200, 38400, 76800, 115.2k
baud rate EIA-485 physical layer
1200 m (max) cable length
LED Indication
Module Status Off = No power
Green = Power normal function
Flashing Green = Gateway is
connected via USB
Flashing Red = Fatal error
Network Status Off = No IP address
Green = Has IP and connection
Flashing Green = Has IP no
Connection
Red = Critical Fail / Duplicate IP
Flashing Red = Connection time
out
Alternating Red/Green = Start up
RS485 Green (TX) = Transmitting data
Red (RX) = Receiving data
Operating Temperature 14 to 122°F (-10 to 50°C)
Operating Humidity 20 to 90% non-condensing
Dimensions 4" x 3" x 1.5"
(10.16 x 7.62 x 3.81 cm)
Weight 1 lb (0.45 kg)
RoHS Statement Ye s
Warranty 1 year
MODEL DESCRIPTION
ETH-1000 Provides protocol translation between Ethernet and RS-485 based networks
SPECIFICATIONS
DESCRIPTION
The ETH-1000 Ethernet Gateway allows information to be
transferred seamlessly between Ethernet and RS-485 networks
with minimal configuration requirements. The ETH-1000
provides a 10/100BaseT Ethernet port and an RS-485 port.
ETHERNET PROTOCOLS SUPPORT:
• Allen Bradley CSP (also known as "PCCC" and "AB
Ethernet") (client and server)
• BACnet/IP (client and server)
• EtherNet/IP (client and server)
• Mitsubishi MELSEC (also known as "MC") (client)
• Modbus/TCP (client and server)
• Profinet IO
ETH-1000
RS-485 PROTOCOLS SUPPORT:
• Modbus RTU (master, slave, and sniffer)
• BACnet MS/TP (client and server)
• Toshiba ASD (master)
• Johnson Controls, Inc. Metasys N2 (slave)
• Sullair Supervisor (master)
RELATED PRODUCTS PAGE
XLTR-1000 Provides protocol translation between RS485 based networks 714
WIRING