Specifications
NEW!
NETWORK & WIRELESS
732
NEW!
NETWORK & WIRELESS
13
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
ORDERING INFORMATION
LON SWITCH ROUTER
L-SWITCH SERIES
-
12-35 VDC
12-24 VAC
+
CEA-709
Port 2
Termination
(L-Term)
CEA-709
Port 1
123456 15 16 17
POWERFT
Serial Terminal
(Console Connector)
RESET
ACTACT
POWER
STATUS
Connectors
CEA-709 1 Input EARTH GND port 2
2 Input B port 2
3 Input A port 2
CEA-709 4 Input EARTH GND port 1
5 Input B port 1
6 Input A port 1
POWER 15 Power supply input EARTH GND
16 Power supply input MINUS
17 Power supply input PLUS
Do NOT connect to
EARTH GND
SERIAL 40 RS-232 Interface (DB9 male)
Buttons
teseR TESER
STATUS Send service pin message
Status LEDs
A Green flashing fast Traffic port 2
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 2
B Green flashing fast Traffic on port 1
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 1
G Green Power
H OFF Normal operation
40
A
B
G
H
FT
WIRING
MODEL DESCRIPTION
LS-11333CB L-Switch 2 x TP/XF-1250, 3 x TP/FT-10
LS-11CB L-Switch 2 x TP/XF-1250
LS-13300CB L-Switch 1 x TP/XF-1250, 2 x TP/FT-10
LS-13333CB L-Switch 1 x TP/XF-1250, 4 x TP/FT-10
LS-13CB L-Switch 1 x TP/XF-1250, 1 x TP/FT-10
LS-33300CB L-Switch 3 x TP/FT-10
LS-33CB L-Switch 2 x TP/FT-10
LS-xxCB
CEA-709
Port 4
T
ermination
(L-T
erm)
CEA-709
Port 3
CEA-709
Port 2
CEA-709
Port 1
-
12-35 VDC
12-24 VAC
+
CEA-709
Port 5
ACT ACT ACT ACT
RESET
Serial Terminal
(Console Connector)
POWER
40
STATUS
A
D
C
B
I
J
ACT
E
456789 24 25 26
POWER
Connectors
CEA-709 1 Input EARTH GND port 5
2 Input B port 5
3 Input A port 5
CEA-709 4 Input EARTH GND port 4
5 Input B port 4
6 Input A port 4
CEA-709 7 Input EARTH GND port 3
8 Input B port 3
9 Input A port 3
CEA-709 10 Input EARTH GND port 2
11 Input B port 2
12 Input A port 2
CEA-709 13 Input EARTH GND port 1
14 Input B port 1
15 Input A port 1
POWER 24 Power supply input EARTH GND
25 Power supply input MINUS
26 Power supply input PLUS
Do NOT connect to
EARTH GND
SERIAL 40 EIA-232 (DB9 male)
Buttons
RESET Reset
STATUS Send service pin message
Status LEDs
A Green flashing fast Traffic port 5
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 5
B Green flashing fast Traffic on port 4
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 4
C Green flashing fast Traffic on port 3
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 3
D Green flashing fast Traffic on port 2
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 2
E Green flashing fast Traffic on port 1
Green flashing at Port not commissioned
1 HZ
Red permanent CEA-709 port damaged
Red flashing fast Traffic overload on port 1
I Green Power
J OFF Normal operation
10 11 12 13 14 15123
FT FT FT FT
FT
LS-xxxxxCB