Specifications
NEW!
729
NETWORK & WIRELESS
NETWORK & WIRELESS
13
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
BACNET/IP AND LON/IP ROUTER
L-IP SERIES
WIRING
LIP-xECTB
LIP-xxECRB
LIP-xxECTB
10/100Base-T
(RJ45)
-
12-35 VDC
12-24 VAC
+
Termination
(L-Term)
CEA-709
CEA-852
4568 15 16 17
POWEREthernet
Serial Terminal
RESET
LINK
ACT
ACT
CNIP
Ethernet
Server
POWER
STAT
US
40
B
C
F
E
D
G
H
FT
Connectors
CEA-709 4 Input EARTH GND port 1
5 Input B port 1
6 Input A port 1
Ethernet 8 10/100Base-T (RJ45)
POWER 15 Power supply input EARTH GND
16 Power supply input MINUS
17 Power supply input PLUS
Do NOT connect to
EARTH GND
SERIAL 40 EIA-232 (DB9 male)
Buttons
RESET Reset
STATUS Send service pin message
Status LEDs
B Green flashing fast Traffic on port 1
Green flashing at
1 HZ
Red permanent
Red flashing fast
Green
Yellow
Red
Flashing at 1 Hz
OFF
Port not commissioned
CEA-709 port damaged
Traffic overload on port 1
IP port is fully functional
IP port functional but
config. is not up-to-date
IP port in non-functional
IP port is not commissioned
IP port is not active
C
D Green Ethernet link
E Green flashing Ethernet traffic
F Green BBMD enabled
G Green Power
H OFF Normal operation
10/100Base-T
(RJ45)
-
12-35 VDC
12-24 VAC
+
Termination
(L-Term)
CEA-709
Loop
Side 1
CEA-852
4568 15 16 17
POWEREthernet
Serial Terminal
RESET
LINK
ACTPRIM
ACT
CNIP
Ethernet
Server
POWER
STATUS
40
B
A
C
F
E
D
G
H
FT
123
FT
CEA-709
Loop
Side 2
Connectors
CEA-709 1 Do not connect
2 Input B loop side 2
3 Input A loop side 2
CEA-709 4 Input EARTH GND port 2
5 Input B loop side 1
6 Input A loop side 1
Ethernet 8 10/100Base-T (RJ45)
POWER 15 Power supply input EARTH GND
16 Power supply input MINUS
17 Power supply input PLUS
Do NOT connect to
EARTH GND
SERIAL 40 EIA-232 (DB9 male)
Buttons
RESET Reset
STATUS Send service pin message
Status LEDs
A Green Device is active
Off
Orange
Red
Green flashing fast Traffic on CEA-709 loop
Green flashing at
1 HZ
Red permanent
Red flashing fast
Green
Yellow
Red
Flashing at 1 Hz
OFF
Device is inactive (standby)
Problem with twin router
Device is inactive due to
error
Port not commissioned
CEA-709 port damaged
Loop open/Traffic overload
IP port is fully functional
IP port functional but
config. is not up-to-date
IP port in non-functional
IP port is not commissioned
IP port is not active
B
C
D Green Ethernet link
E Green flashing Ethernet traffic
F Green BBMD enabled
G Green Power
H OFF Normal operation
10/100Base-T
(RJ45)
-
12-35 VDC
12-24 VAC
+
Termination
(L-Term)
CEA-709
Port 1
CEA-852
4568 15 16 17
POWEREthernet
Serial Terminal
RESET
LINK
ACT
ACT
CNIP
Ethernet
Server
POWER
STAT
US
40
B
C
F
E
D
G
H
FT
123
FT
CEA-709
Port 2
Connectors
CEA-709 1 Input EARTH GND port 2
2 Input B port 2
3 Input A port 2
CEA-709 4 Input EARTH GND port 1
5 Input B port 1
6 Input A port 1
Ethernet 8 10/100Base-T (RJ45)
POWER 15 Power supply input EARTH GND
16 Power supply input MINUS
17 Power supply input PLUS
Do NOT connect to
EARTH GND
SERIAL 40 EIA-232 (DB9 male)
Buttons
RESET Reset
STATUS Send service pin message
Status LEDs
A Green flashing fast Traffic on port 2
Green flashing at
1 HZ
Red permanent
Red flashing fast
Green flashing fast Traffic on port 1
Green flashing at
1 HZ
Red permanent
Red flashing fast
Green
Yellow
Red
Flashing at 1 Hz
OFF
Port not commissioned
CEA-709 port damaged
Traffic overload on port 2
Port not commissioned
CEA-709 port damaged
Traffic overload on port 1
IP port is fully functional
IP port functional but
config. is not up-to-date
IP port in non-functional
IP port is not commissioned
IP port is not active
B
C
D Green Ethernet link
E Green flashing Ethernet traffic
F Green BBMD enabled
G Green Power
H OFF Normal operation