Specifications

NEW!
NETWORK & WIRELESS
722
NEW!
NETWORK & WIRELESS
13
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
BACNET AND LON TOUCH PANEL
L-VIS SERIES
Mounting Frame
L-VIS Touch Panel
12.1”: LVIS-FRAME12
15”: LVIS-FRAME15
5-7”: LVIS-FRAME1
INSTALLATION
Status LEDs
ACT709 GREEN flashing fast Traffic on CEA-709 port
GREEN flashing at 1 Hz CEA-709 port not commissioned
RED permanent CEA-709 port is damaged
RED flashing fast Traffic overload on CEA-709 port
CNIP GREEN IP port is fully functional
YELLOW IP port functional but config. is not up-to-date
RED IP port is non-functional
Flashing at 1Hz IP port not commissioned
OFF IP port not active
LINK GREEN Ethernet link
CN/IP GREEN flashing Traffic on BACnet IP port
MS/TP GREEN flashing Traffic on BACnet MS/TP port
ACT GREEN flashing Ethernet traffic
ONLINE GREEN Node is in configured online state
PWR GREEN Power
STAT OFF Normal operation
LVIS-3E100 Buttons
RESET Reset
STATUS Send service pin message
STAT
PWR
STATUS
RESET
ONLINE
CNIP, CN/IP
ACT709, MS/TP
ACT
LINK
LVIS-ME Buttons
RESET Reset
STATUS Send “I AM” message
WIRING
0,2 - 2,5 mm
2
Weidmüller BLZP 5.08/03/180
7
Ethernet
100Base-T
+-
20-35 VDC
24 VAC +/-10%
TEMP
123456
7
8910 11 12 13
SWITCH POWER
EARTH
JP1 JP2
L-TEMP
External
temperature
sensor
MS/TP
or
CEA-709 (LON
)
RS-485
or
FT/LPT (LON)
Jumpers
JP1 Normal operation
Clear configuration
JP2 MS/TP channel active/FT-10/
LPT-10 channel active
BIP channel active/CEA-852
(IP-10) channel active
Connectors
1 Temperatur sensor data
2 Temperatur sensor GND
3 Temperatur sensor +3V
4 MS/TP input GND/CEA-709 input EARTH GND
5 MS/TP +/CEA-709 input B
6 MS/TP -/CEA-709 input A
7 Ethernet 10/100 Base-T (RJ45)
8 Digital input GND
9 Digital input 1
10 Digital input 0
11 Power supply input earth ground
12 Power supply input MINUS
13 Power supply input PLUS
Do not connect PLUS to GND
L-VIS 5.7" PANEL
March 2014