Redundant power supply modules Q63RP and Q64RP
When power is switched on again immediately (within 5 seconds) after power-off, an inrush current of more than
the specified value (2 ms or less) may flow.
Reapply power 5 or more seconds after power-off.
When selecting a fuse and breaker in the external circuit, take account of the blowout, detection characteristics
etc.
Overcurrent protection
The overcurrent protection device shuts off the 5 V, 24 V DC circuit and stops the system if the current flowing in
the circuit exceeds the specified value.
The LED of the power supply module turns off or turns on in dim green when voltage is lowered. If this device is
activated, switch the input power supply off and eliminate the cause such as insufficient current capacity or short.
Then, a few minutes later, switch it on to restart the system.
Overvoltage protection
The overvoltage protection device shuts off the 5 VDC circuit and stops the system if a voltage of 5.5 V DC is
applied to the circuit.
When this device is activated, the power supply module LED turns on in red. If this happens, switch the input
power off, then a few minutes later on. This causes the initial start for the system to take place. The power supply
module must be changed if the system is not booted and the LED remains red.
Item Q63RP Q64RP
Mounting position Power supply module mounting slot "POWER"
Applicable base unit Q3
RB, Q6
RB, Q6
WRB,
Input power sup-
ply
V AC
(+10 %, -15 %)
100 to 240
V DC
(+30 %, -35 %)
24
Input frequency 50/60 Hz (
±
5 %)
Maximum input apparent power 65 W 160 VA
Inrush current
150 A within 1 ms 20 A within 8 ms
Rated output cur-
rent
5 V DC 8.5 A 8.5 A
24 V DC
External output voltage
Overcurrent pro-
tection
5 V DC
9.35 A
24 V DC
Overvoltage protection
5.5 to 6.5 V
Efficiency
65 %
Dielectric withstand voltage (Across
primary and secondary connection)
500 V AC, 1 min 2830 V AC, 1 min
Operation indication The "POWER" LED turns on in green, when the output voltage is present.
Contact output
section
Application Error contact (refer to chapter 7)
Rated switching
voltage, current
24 V DC; 0.5 A
Minimum
switching load
5 V DC; 1 mA
Response time OFF
ON:
10 ms
ON
OFF:
12 ms
Life Mechanical: More than 20 million times
Electrical: More than 100 thousand times at rated switching voltage, current
Overvoltage
protection
Fuse The signal output is not protected by fuse.
Terminal screw size M3.5
Applicable wire size
0.75 to 2 mm
2
Applicable tightening torque 66 to 89 Ncm
External dimensions (HxWxD)
[mm]
98x83x115
Weight 0.60 kg 0.47 kg
Allowable momentary power failure
period
10 ms 20 ms
Tab. 12-69: Redundant power supply module of MELSEC System Q specifications