User`s manual
Specifications Input/output module specifications
12 – 12
12.3.5 Digital input module QX40-TS
The response times OFF –> ON and ON –> OFF can’t be set to different values.
Item QX40-TS
Number of input points 16
Isolation method Photocoupler
Rated input voltage 24 V DC (+20/–15 %, ripple ratio within 5 %)
Rated input current approx. 4 mA
Max. simultaneously ON All inputs can be switched on simultaneously.
Inrush current —
ON voltage/ON current
≥
19 V DC /
≥
3 mA
OFF voltage/OFF current
≤
11 V DC /
≤
1.7 mA
Input impedance approx. 5.6 k
Ω
Response time
OFF
→
ON 1, 5, 10, 20, 70 ms
(Response time setting by parameters, initial setting: 10 ms)
ON
→
OFF 1, 5, 10, 20, 70 ms
(Response time setting by parameters, initial setting: 10 ms)
Groups of input 1; 16 points/common
(common terminal: 17)
Input status display One LED per input
Dielectric withstand voltage 560 V AC rms/3 cycles (altitude 2000 m)
External connections Removable terminal block with spring terminals
Applicable wire size
0.3 to 2.0 mm
2
, core (outside diameter: 1.45 mm max.)
Internal current consumption
(5 V DC)
50 mA (all input points ON)
Weight 0.16 kg
External connections
Terminal
block
number
Signal
1X00
2X01
3X02
4X03
5X04
6X05
7X06
8X07
9X08
10 X09
11 X0A
12 X0B
13 X0C
14 X0D
15 X0E
16 X0F
17 COM
18 Vacant
Tab. 12-12: Input module QX40-TS
Internal
circuit
LED
1
16
17
24 V DC
Input module
+