Troubleshooting Error code list
11 – 90
6130
TRK. DISCONNECT
– The tracking cable was removed.
– The tracking cable became faulty while the
CPU module is running.
– The CPU module side tracking hardware
became faulty.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
– If the tracking cable was removed, connect
the tracking cable to the connectors of the
CPU modules of the two systems.
– When the error is not resolved after connect-
ing the tracking cable to the connectors of the
CPU modules of the two systems and reset-
ting the error, the tracking cable or CPU mod-
ule side tracking hardware is faulty.
Contact your local Mitsubishi representative.
ON ON Continue QnPRH
6140
TRK.INIT. ERROR
– The other system did not respond during ini-
tial communication at power ON/reset.
– The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/At reset
– Power the corresponding CPU module OFF
and then ON again, or reset it and then unre-
set. If the same error still occurs, this indi-
cates the CPU module is faulty.
Contact your local Mitsubishi representative.
– Confirm the redundant system startup proce-
dure, and execute a startup again.
OFF Flicker Stop QnPRH
6200
CONTROL EXE.
The standby system has been switched to the
control system in a redundant system. (Detected
by the CPU that was switched from the standby
system to the control system). Since this error
code does not indicate the error information of
the CPU module but indicates its status, the
error code and error information are not stored
into SD0 to SD26, but are stored into the error
log every system switching. (Check the error
information by reading the error log using GX
(IEC) Developer.)
Collateral information
Common Information: Reason(s) for system
switching
Individual Information: —
Diagnostic Timing
Always
—
ON OFF No error QnPRH
6210
STANDBY
The control system has been switched to the
standby system in a redundant system.
(Detected by the CPU that was switched from the
standby system to the control system). Since
this error code does not indicate the error infor-
mation of the CPU module but indicates its sta-
tus, the error code and error information are not
stored into SD0 to SD26, but are stored into the
error log every system switching. (Check the
error information by reading the error log using
GX (IEC) Developer.)
Collateral information
Common Information: Reason(s) for system
switching
Individual Information: —
Diagnostic Timing
Always
—
ON OFF No error QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-8: Error code list (6000 to 6999) for PLC CPUs of MELSEC System Q