User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 61
3101
LINK PARA. ERROR
The link refresh range exceeded the file register
capacity.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
When an END instruction executed
Change the file register file for the one that ena-
bles entire range refresh.
OFF Flicker Stop Qn(H)
(Function
version is B or
later)
QnPH
QnPRH
QnU (except
Q00UJCPU)
LINK PARA. ERROR
When the station number of the MELSECNET/
H module is 0, the PLC-to-PLC network
parameter has been set.
When the station number of the MELSECNET/
H module is other than 0, the remote master
parameter setting has been made.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Correct the type or station number of the
MELSECNET/H module in the network parameter
to meet the used system.
OFF Flicker Stop Qn(H)
(Function
version is B or
later)
QnPH
QnPRH
LINK PARA. ERROR
The refresh parameter for the CC-Link IE control-
ler network is outside the range.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Check the network parameters and actual
mounting status, and if they differ, make them
match.
When network parameters are modified, write
them to the CPU module.
Check the setting of extension base unit stage
number.
Check the connection status of extension
base unit and extension cables. When the
GOT is busconnected to the main base unit or
extension base unit, also check its connection
status.
If the error occurs even after the above checks,
the possible cause is a hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop Qn(H) (first 5
digits of serial
No. is 09012 or
later)
QnPH (first 5
digits of serial
No. is 10042 or
later)
QnPRH (first 5
digits of serial
No. is 10042 or
later)
QnU
LINK PARA. ERROR
The network No. specified by a network
parameter is different from that of the actually
mounted network.
The head I/O No. specified by a network
parameter is different from that of the actually
mounted I/O unit.
The network class specified by a network
parameter is different from that of the actually
mounted network.
The network refresh parameter of the
MELSECNET/H, MELSECNET/10 is out of the
specified area.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
OFF Flicker Stop
)
LINK PARA. ERROR
A multi-remote I/O network was configured
using a module that does not support a multi-
remote I/O network.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Use a module that supports a multi-remote I/O
network.
OFF Flicker Stop QnPH
LINK PARA. ERROR
The system A of the MELSECNET/H remote
master station has been set to other than Sta-
tion No. 0.
The system B of the MELSECNET/H remote
master station has been set to Station No. 0.
Collateral information
Common Information: File name/Drive name
Individual Information: Parameter No.
Diagnostic Timing
At power ON/At reset/STOP
RUN
Set the system A of the MELSECNET/H
remote master station to Station No. 0.
Set the system B of the MELSECNET/H
remote master station to any of Station No. 1
to 64.
OFF Flicker Stop QnPRH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-5: Error code list (3000 to 3999) for PLC CPUs of MELSEC System Q