User`s manual

Troubleshooting Error code list
11 – 52
2501
CAN’T EXE. PRG.
There are multiple program files although "none"
has been set at the PLC parameter program set-
tings.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Edit the PLC parameter program setting to
"yes".
Alternatively, delete unneeded programs.
OFF Flicker Stop Qn(H)
QnPH
QnPRH
QnU
CAN’T EXE. PRG.
There are three or more program files.
The program name differs from the program
contents.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Delete unnecessary program files.
Match the program name with the program
contents.
OFF Flicker Stop Q00J/Q00/Q01
2502
CAN’T EXE. PRG.
The program file is incorrect.
Alternatively, the file contents are not those of
a sequence program.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Check whether the program version is ***.QPG,
and check the file contents to be sure they are for
a sequence program.
OFF Flicker Stop
)
CAN’T EXE. PRG.
The program file is not the one for the redundant
CPU.
Alternatively, the file contents are not those of
a sequence program.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Create a program using GX Developer, GX IEC
Developer or PX Developer for which the PLC
type has been set to the redundant CPU
(Q12PRH/Q25PRH), and write it to the CPU
module.
OFF Flicker Stop QnPRH
2503
CAN’T EXE. PRG.
There are no program files at all.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Check program configuration.
Check parameters and program configuration.
OFF Flicker Stop
)
2504
CAN’T EXE. PRG.
Two or more SFC normal programs or control
programs have been designated.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Check program configuration.
Check parameters and program configuration.
OFF Flicker Stop Qn(H)
QnPH
QnPRH
QnU
CAN’T EXE. PRG.
There are two or more SFC programs.
Collateral information
Common Information: File name/Drive name
Individual Information: —
Diagnostic Timing
At power ON/At reset/STOP
RUN
Reduce the SFC programs to one.
OFF Flicker Stop Q00J/Q00/Q01
(Function
version is B or
later)
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-4: Error code list (2000 to 2999) for PLC CPUs of MELSEC System Q