User`s manual

Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 43
2111
SP UNIT ERROR
The location designated by a link direct device
(J\) is not a network module.
The I/O module (intelligent function module/
special function module) was nearly removed,
completely removed, or mounted during run-
ning.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: Program error loca-
tion
Diagnostic Timing
When instruction executed.
Read the individual information of the error
using the GX (IEC) Developer, check the
FROM/TO instruction that corresponds to that
numerical value (program error location), and
correct when necessary.
The intelligent function module/special func-
tion module that was accessed is experienc-
ing a hardware fault. Therefore, change the
faulty module. Alternatively, contact your local
Mitsubishi representative.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
)
2112
SP UNIT ERROR
The module other than intelligent function
module/special function module is specified
by the intelligent function module/special
function module dedicated instruction. Or, it is
not the corresponding intelligent function
module/special function module.
There is no network No. specified by the net-
work dedicated instruction. Or the relay target
network does not exist.
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: Program error loca-
tion
Diagnostic Timing
When instruction executed/STOP
RUN
Read the individual information of the error
using the GX (IEC) developer, and check the spe-
cial function module /special function module
dedicated instruction (network instruction) that
corresponds to the value (program error part) to
make modification.
OFF/ON Flicker/
ON
Stop/
Continue
(can be set
in the
parameters
at error
occur-
rence)
)
2113
SP UNIT ERROR
The module other than network module is speci-
fied by the network dedicated instruction.
Collateral information
Common Information: FFFF
H
(fixed)
Individual Information: Program error loca-
tion
Diagnostic Timing
When instruction executed/STOP
RUN
Qn(H)
QnPH
2114
SP UNIT ERROR
An instruction, which on execution specifies
other stations, has been used for specifying the
host CPU. (An instruction that does not allow the
host CPU to be specified).
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: Program error loca-
tion
Diagnostic Timing
When instruction executed/STOP
RUN
Read the individual information of the error
using the GX (IEC) Developer, check the program
corresponding that value (program error loca-
tion), and make correction.
OFF/ON Flicker/
ON
Stop/
Continue
Q00J/Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
QnU
2115
SP UNIT ERROR
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other
stations to be specified).
Collateral information
Common Information: Module No. (Slot No.)
Individual Information: Program error loca-
tion
Diagnostic Timing
When instruction executed/STOP
RUN
Read the individual information of the error
using the GX (IEC) Developer, check the program
corresponding that value (program error loca-
tion), and make correction.
OFF/ON Flicker/
ON
Stop/
Continue
Q00J/Q00/Q01
(Function
version is B or
later)
Qn(H)
(Function
version is B or
later)
QnPH
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-4: Error code list (2000 to 2999) for PLC CPUs of MELSEC System Q