User`s manual
Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 31
1200
OPE. CIRCUIT ERR.
The operation circuit for index modification in
the CPU module does not operate normally.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
This suggests a CPU module hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop
)
1201
OPE. CIRCUIT ERR.
The hardware (logic) in the CPU module does
not operate normally.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
1202
OPE. CIRCUIT ERR.
The operation circuit for sequence processing in
the CPU module does not operate normally.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At reset
1203
OPE. CIRCUIT ERR.
The operation circuit for index modification in
the CPU module does not operate normally.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When an END instruction executed
This suggests a CPU module hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop QnPRH
1204
OPE. CIRCUIT ERR.
The hardware (logic) in the CPU module does
not operate normally.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When an END instruction executed
1205
OPE. CIRCUIT ERR.
The operation circuit for sequence processing in
the CPU module does not operate normally.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When an END instruction executed
1300
FUSE BREAK OFF
There is an output module with a blown fuse.
Collateral information
Common Information:
Module No.(Slot No.); For Remote I/O net-
work: Network No./Station No.
Individual Information: —
Diagnostic Timing
Always
– Check FUSE LED of the output modules and
replace the module whose LED is lit.
(The module with a blown fuse can also be
identified using GX (IEC) Developer. Check the
special registers SD1300 to SD1331 to see if
the bit corresponding to the module is "1".)
– When a GOT is bus-connected to the main
base unit or extension base unit, check the
connection status of the extension cable and
the earth status of the GOT.
OFF/ON Flicker/
ON
Stop/
Continue
(CPU oper-
ation can
be set in
the param-
eters at
error
occur-
rence)
Qn(H)
QnPH
QnPRH
QnU
Check ERR. LED of the output modules and
replace the module whose LED is lit.
(The module with a blown fuse can also be iden-
tified using GX (IEC) Developer. Check the spe-
cial registers SD130 to SD137 to see if the bit
corresponding to the module is "1".)
Q00J/Q00/Q01
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-3: Error code list (1000 to 1999) for PLC CPUs of MELSEC System Q