User`s manual
Error code list Troubleshooting
MELSEC System Q, Hardware 11 – 27
1010
END NOT EXECUTE
Entire program was executed without the execu-
tion of an END instruction.
– When the END instruction is executed it is
read as another instruction code, e.g. due to
noise.
– The END instruction has been changed to
another instruction code somehow.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When an END instruction executed
– Take noise reduction measures.
– Reset the CPU module and RUN it again. If the
same error is displayed again, this suggests a
CPU module hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop
)
1020
SFCP. END ERROR
The SFC program cannot be normally terminated
due to noise or other reason.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
When SFC program is executed
– Take noise reduction measures.
– Reset the CPU module and RUN it again. If the
same error is displayed again, this suggests a
CPU module hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop Q00J/Q00/Q01
(Function
version is B or
later)
QnPH
QnU
1035
MAIN CPU DOWN
Runaway or failure of CPU module or failure of
main CPU
– Malfunctioning due to noise or other reason
– Hardware fault
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
Always
– Take noise reduction measures.
– Reset the CPU module and RUN it again. If the
same error is displayed again, this suggests a
CPU module hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop QnU
1101
RAM ERROR
The sequence program storing program memory
in the CPU module is faulty.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At Reset/ When an END instruction
executed
– Take noise reduction measures.
– Reset the CPU module and RUN it again. If the
same error is displayed again, this suggests a
CPU module hardware fault.
Contact your local Mitsubishi representative.
OFF Flicker Stop
)
1102
RAM ERROR
– The work area RAM in the CPU module is
faulty.
– The standard RAM and extended RAM in the
CPU module are faulty.
Collateral information
Common Information: —
Individual Information: —
Diagnostic Timing
At power ON/ At Reset/ When an END instruction
executed
OFF Flicker Stop
Error
code
Error contents and cause Corrective action
LED status
CPU
status
Corre-
sponding
CPU
RUN ERR.
Tab. 11-3: Error code list (1000 to 1999) for PLC CPUs of MELSEC System Q