User`s manual

1 - 4
1.1 Features
1
OVERVIEW
(3) Enriched operation history and error history
The CPU module can record a total of 3000 operation/error history entries for the
details of the CPU module operation by the user and for the errors occurred in the
CPU module or the CC-Link Safety system.
Recording the details of the CPU module operation by the user into the operation/
error history clarifies the occurrence order of operations and errors. Troubleshooting
becomes easier by confirming the error/operation history.
The contents recorded in the operation/error history are shown in Table1.2.
Table1.2 Recorded contents of operation/error history
Information Contents History Information per Entry
Operation
history
information
User's operations for the CPU module are
stored as a history.
(Operations which change the CPU module
status are recorded.)
Operation code
Operation message
Operation execution date
Result code
Operation attached information
Error history
information
The following errors are stored as a history.
Error/failure detected by self-diagnostics
Hardware error
Error detected by CC-Link Safety system
Error code
Error message
Occurrence date
Error information category (common
information/individual information)
Error information (common