User`s manual
6 - 42
6.10 Setting of Output (Y) Status when Changing between STOP and RUN
6
FUNCTIONS
(3) Operation switching from STOP status to RUN status
(a) Output (Y) status prior to STOP is output (Default)
After the output (Y) status before the STOP status is output, the sequence
program calculations are performed.
(b) Output is cleared
The output becomes OFF status.
The output (Y) is output after the operation of sequence program.
Refer to (5) for the operation when performing forced ON of output(Y) at STOP
status.
Diagram 6.21 Processing when Change from STOP Status to RUN Status
STOP status RUN status
Clear the output (Y) status.
YES (Set "Previous state". (default))
Output the output (Y) status right
before changing to STOP status.
Execute the sequence
program calculations.
NO (Set "Recalculate".)
Is "Previous state" set?