Specifications
Allen-Bradley DF1 Driver Help
Error writing to address '<address>' on device '<device name>'. Slave source
empty
Error Type:
Serious
Possible Cause:
The slave device does not have a response prepared for the write request to address < address>. The slave re-
poll delay may be set to short.
Solution:
The driver will automatically poll and re-poll the slave in seek of a poll response. If this error occurs too often,
increase the slave re-poll delay on the given channel.
Device '<device name>' timed out writing to address '<address>'
Error Type:
Serious
Possible Cause:
1. The device is not responding.
2. The serial connection between the device and the Host PC is broken.
Solution:
Inspect cabling between the Host PC and the device. Verify the device is on and operating properly.
Unable to read data starting at <start address> on device '<device name>'.
Device replied with a NAK
Error Type:
Serious
Possible Cause:
The server sent an invalid response or one of unexpected size.
Solution:
If this error occurs frequently, contact Technical Support.
Unable to read function file <fun. file element> on device '<device name>'.
Device replied with a NAK
Error Type:
Serious
Possible Cause:
The server sent an invalid response or one of unexpected size.
Solution:
If this error occurs frequently, contact Technical Support.
Unable to read data starting at <start address> on device '<device name>'.
Memory map error
Error Type:
Serious
Possible Cause:
There was an error writing to memory on the server.
Solution:
If this error occurs frequently, contact Technical Support.
www. kepware.com
51