Datasheet
59
BlueNet / Power Unit 2 U
Two galvanically isolated
infeeds
2 U high, 19" wide
(1 U is 44.45mm)
A built-in Ethernet port lets you
export readings and set alarm
thresholds via a web browser
or SNMP.
The measurement module can be replaced
during operation without interrupting the supply
to the connected devices.
Current, effective power,
voltage, frequency, phase
angle and energy can be
read from the LC display
on the front of the unit.
LEDs indicate whether
there is voltage present
on each of the phases.
Power measurement (kW)
The effective power drawn by the
consumers, taking the phase angle into
account. Power consumption of the
connected devices.
Mains voltage (V)
Displays the voltage of the incoming
mains supply to which the power meter is
connected.
Phase angle
Displays the phase shift in the
power network.
Frequency (H z)
Current mains frequency
Phase indicator (P)
Shows the phase (1, 2 or 3) currently
being measured. Display moves
automatically through the phases
showing their respective measured
values.
Current (A)
The current now being
drawn by the connected
devices.
Total energy
consumption (kWh)
The total energy
consumption shown on
the display is calculated
taking the phase angle
into account.
BlueNet Power Unit
BlueNet