Datasheet
IT POWER SOLUTIONS
46
BlueNet / BN3000master – slave
BlueNet BN3000 is the next generation of BlueNet products. An optimised shape factor, PDUs that can be
cascaded via Modbus and a rotatable OLED display create the ideal basis for the energy monitoring system
of the future.
The data centre's mains supply is monitored and remotely controlled from the comfort of your desk with
BlueNet Network products. BlueNet increases data centre availability, minimises down times and cuts costs.
BlueNet monitors current, voltage and power. This allows resources to be planned efficiently and alarms to
be issued in the event of faults.
BlueNet BN3000master / slave
16 - 32 A / 230 - 400 V / 50 Hz
L1 12.1 A
L2 12.0 A
L3 11.4 A
ESC
ACTIVE
CURRENT
Overview
Shows the measured
values of all phases in an
overview.
Scrolling
The keys on the front can
be used to scroll through
the various measured
values.
Display can be rotated
The display can be rotated in 90°
steps so it is easier to read.
Integrated display
The most important measured
values at rack level at a glance.
Measurement
Current, power (effective, apparent and reactive
power), energy consumption, voltage, frequency,
power factor, N conductor
∙ PDUs can be cascaded via Modbus, just one Ethernet connection is needed for 10 PDUs
∙ Incredibly compact design (1 U wide x 60mm deep), rotatable OLED display
∙ Robust housing made from torsionally rigid aluminium profile
∙ 1-phase and 3-phase versions
∙ 3.6 kW - 22 kW power range
∙ Coloured phase assignment of socket inserts
∙ Measurement of: current, power (effective, apparent and reactive power), energy consumption,
voltage, frequency,
∙ power factor, N conductor
∙ Measurement per phase
∙ Option for connecting external sensors (temperature / air humidity)
∙ Operated locally or using web browser via Ethernet port
∙ Protocols: HTTP, SNMP, Ethernet 10/100 MBit/s, DHCP, NTP
∙ Accuracy of measurement +/- 1 %
∙ Internal consumption < 4 W
The benefits at a glance