Datasheet

IT POWER SOLUTIONS
46
BlueNet / BN3000master – slave
BlueNet BN3000 is the next generation of BlueNet products. An optimised shape factor, PDUs that can be
cascaded via Modbus and a rotatable OLED display create the ideal basis for the energy monitoring system
of the future.
The data centre's mains supply is monitored and remotely controlled from the comfort of your desk with
BlueNet Network products. BlueNet increases data centre availability, minimises down times and cuts costs.
BlueNet monitors current, voltage and power. This allows resources to be planned efficiently and alarms to
be issued in the event of faults.
BlueNet BN3000master / slave
16 - 32 A / 230 - 400 V / 50 Hz
L1 12.1 A
L2 12.0 A
L3 11.4 A
ESC
ACTIVE
CURRENT
Overview
Shows the measured
values of all phases in an
overview.
Scrolling
The keys on the front can
be used to scroll through
the various measured
values.
Display can be rotated
The display can be rotated in 90°
steps so it is easier to read.
Integrated display
The most important measured
values at rack level at a glance.
Measurement
Current, power (effective, apparent and reactive
power), energy consumption, voltage, frequency,
power factor, N conductor
PDUs can be cascaded via Modbus, just one Ethernet connection is needed for 10 PDUs
Incredibly compact design (1 U wide x 60mm deep), rotatable OLED display
Robust housing made from torsionally rigid aluminium profile
1-phase and 3-phase versions
3.6 kW - 22 kW power range
Coloured phase assignment of socket inserts
Measurement of: current, power (effective, apparent and reactive power), energy consumption,
voltage, frequency,
power factor, N conductor
Measurement per phase
Option for connecting external sensors (temperature / air humidity)
Operated locally or using web browser via Ethernet port
Protocols: HTTP, SNMP, Ethernet 10/100 MBit/s, DHCP, NTP
Accuracy of measurement +/- 1 %
Internal consumption < 4 W