Sensor Replacement
Over time the sensor will become less responsive to refrigerant gas as it
nearstheendofitsusefullife.Asensor’saveragelifeexpectancyisap-
proximately150hoursor1yearofnormaluse,butwillvarydependingon
the amount of refrigerant that passes through the sensor.
Replacethesensorasfollows(seeFigure4):
Material Required:
•Sensor(refertoSectionReplacement Parts)
Procedure:
1. Turn OFF instrument.
2. Grasp nose cone of probe assembly and pull probe away from case
using a slight twisting motion.
3. Sensor may be hot! Pull spent sensor from its socket and discard.
4. Pluginnewsensor.
5. Pushprobeassemblybackintocase.
6. Turn ON the instrument and check that it responds in a positive man-
ner to a source of refrigerant gas.
Maintenance
Figure 4. Sensor Replacement
Grasp probe assembly’s nose
cone and pull probe away from
case while applying a slight
twisting motion.
REFRIGERANT
SENSOR