TROUBLESHOOTING
G
UIDE
PROBLEM
LED STATUS
POSSIBLE CAUSE SOLUTION
FLUOROMIZER
COMPRESSOR WILL
NOT START
• Green LED VACUUM PRESSURE SWITCH HAS
BEEN ACTIVATED
TURN FLUOROMIZER OFF.
APPLY 1-2 PSIG PRESSURE TO
INLET PORT TO RESET VACUUM
SWITCH
• Red LED CHECK FOR RESTRICTIONS IN
THE DISCHARGE LINE. ENSURE
THAT THE TANK VALVES AND
DISCHARGE VALVES ARE OPEN
REMOVE RESTRICTIONS IN THE
HIGH SIDE
RECOVERY CYLINDER HAS
REACHED 450 PSI HIGH
PRESSURE LIMIT
REPLACE WITH EMPTY
CYLINDER OR COOL CYLINDER
WITH WATER/ICE
• Green LED BAD THERMAL OVERLOAD CALL BACHARACH TEST
SYSTEMS FOR SERVICE
• NONE CIRCUIT BREAKER IS TRIPPED RESET CIRCUIT BREAKER
NO POWER TO THE FLUOROMIZER PLUG THE FLUOROMIZER INTO A
110-120 VOLT POWER SOURCE
FLUOROMIZER FAN
WILL NOT START
• Green LED DEFECTIVE FAN REPLACE FAN
OBSTRUCTION IN FAN BLADES REMOVE OBSTRUCTION
• NONE SYSTEM SWITCH IS OFF TURN SYSTEM AND FAN SWITCH
TO ON POSITION
FLUOROMIZER
STARTS BUT STOPS
AFTER A FEW
MINUTES OF
OPERATION
• LED Off EVACUATION IS COMPLETE CHECK INLET PRESSURE,
VERIFY VACUUM LEVEL IS AT
LEAST 10"HG
IF REFRIGERANT REMAINS IN THE
SYSTEM, CHECK FOR
RESTRICTIONS IN THE SUCTION
LINE
ENSURE ALL VALVES ARE OPEN
• Red LED LIQUID VALVE ON DOT CYLINDER
CLOSED OR OUTLET BALL VALVE
IS NOT OPEN
OPEN THE VALVES
OTHER RESTRICTION(S) IN
DISCHARGE HOSE
TURN UNIT OFF.
REMOVE RESTRICTION
• Green LED CIRCUIT BREAKER TRIPPED DUE
TO COMPRESSOR STALL
REDUCE THE INLET AND/OR
OUTLET PRESSURE
THE UNIT IS TOO HOT. THERMAL
OVERLOAD TRIPPED
LET THE UNIT COOL DOWN FOR
15 MINUTES
CIRCUIT BREAKER TRIPPED DUE
TO TOO MUCH PRESSURE OR
LIQUID IN THE SYSTEM
PURGE THE SYSTEM AND
CONTINUE