Instruction manual
Multi-Zone Gas Monitors
P/N: 3015-5074 53
APPENDIX A. RECOMMENDED REFRIGERANT GAS ALARM
SETTINGS
Gas
Alarm Settings (PPM)
Gas
Alarm Settings (PPM)
Leak Spill Evacuate Leak Spill Evacuate
CO
2
-744 1500 2000 3000 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
N1230 100 300 500 100 300 500
3
-717 50 150 300 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
25 35 50 100 300 500
100 300 500 100 300 500
100 300 500 100 300 500
100 300 500 -717/
3
50 150 300
100 300 500 -744/CO
2
1500 2000 3000
100 300 500