Specifications
Ammonia Gas Monitor – Multi Zone
26
Instruction 3015-5113
Navigating to the 2
nd
Setup Screen
From AGM System Setup Screen #1, select the SYSTEM option to go to AGM System Setup Screen #2.
Select the ESC key to return to the System Setup Screen #1.
AGM System Setup Screen #2
Location
This is the name you assign to the AGM-MZ to identify its location. It may have up to 12 alphanumeric
characters.
1. Press the ENTER key to adjust the setting.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to
modify the individual characters.
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.
Number of Zones Installed
IMPORTANT: Do not change the number of zones to deactivate unused zones. Changing the number of
installed zones is only necessary when manifold blocks are added or removed. Go to the individual zone that
you wish to disable and set its distance to zero.
1. Press the ENTER key to adjust the number.
2. Use the UP/DOWN cursor keys to modify the number.
3. Press ENTER to accept the new number or ESC to revert to the previous setting.
Alarm Ack Mode
This function programs the relays in the AGM unit for latching or non-latching operation.
1. Press the ENTER key to adjust the setting.
2. Use the UP/DOWN cursor keys to toggle between settings.
AUTO – Non-latching (Alarm relay will automatically de-energize when the gas level drops
below its alarm point.)
MANUAL – Latching (Alarm relay remains energized, and will not release until the alarm condition
has been manually acknowledged. Refer to
Acknowledging Alarms
on Page 34.)
3. Press ENTER to accept the new entry or ESC to revert to the previous setting.